Installing the model 8204-E8A or 9409-M50 into a rack

You might need to install the system into a rack. Use the procedure in this section to perform this task. In addition to information intended to promote safety and reliable operation, this section also includes illustrations of the related hardware components and shows how these components relate to each other.

This is a customer task. You can perform this task yourself, or contact a service provider to perform the task for you. You might be charged a fee by the service provider for this service.
Important: To complete this procedure, it is suggested that you use two people to attach the rail assembly to the rack, one in front of the rack and one at the back of the rack. You will need three people to lift the system unit onto the rack.
This procedure assumes that you are installing the system into an existing rack. If the rack is not installed, go to the instructions for Installing the rack and then return to this procedure for instructions on installing the system unit in a rack.
Note: This procedure applies only to the models that are designed to be mounted in a rack. Do not attempt to install a stand-alone model in a rack.

To install the model Installing the model 8204-E8A, or 9409-M50 into a rack into a rack, complete the following steps:

CAUTION:
Installing the rails in the rack is a complex procedure. To install the rails correctly, you must perform each task in the following order. Failure to do so might cause rail failure and potential danger to yourself and the system unit.
  1. Read the Rack safety notices.
  2. If you have not already done so, refer to Figure 1 and complete a parts inventory.
    Figure 1. Rack-mounting kit
    Rack-mounting kit for model 5505/50
    •  A  Rack-mounting hardware kit
      • Four large retaining screws
      • Two medium-sized screws
      • Two nut clips
      • Eight small retaining screws
      • Two rail support brackets
      • Two cable-restraint brackets
    •  B  Left and right rack rails with rack brackets
    •  C  Cable-management arm pins
    •  D  Two cable-management arm brackets (one for left-side installation, one for right-side installation)
    •  E  Cable-management arm
    •  F  Two rack latches
    If there are incorrect, missing, or damaged parts, contact:
    • Your IBM® reseller
    • IBM Rochester Manufacturing Automated Information Line at 1-800-300-8751 (United States only)
    • Directory of worldwide contacts Web site at http://www.ibm.com/planetwideLink outside information center (Locate your service and support telephone numbers.)
  3. Locate the rack-mounting hardware kit (A), and the rack rails (B) that were included with your system unit as shown in Figure 1.

    The system rails (B) are front-to-back and left-to-right side dependent. The rails are labeled left and right to indicate their placement when you face the front of the rack. The back of each rail has two large latch assemblies. These latch assemblies go in the back of the rack.

  4. Determine where you will locate the system unit in the rack. See Determining the location.
  5. Next, you must attach mounting hardware to the rack. For more information, see Attach the mounting hardware to the rack.