Hardware specifications provide detailed information for
your rack, including dimensions, electrical, power, temperature, environment,
and service clearances.
Table 1. Dimensions| Dimensions |
Maximum configuration weight |
Width |
Depth |
Height |
| Metric |
726 kg |
650 mm |
1020 mm |
1800 mm |
| English |
1600 lb |
25.5 in. |
40.1 in. |
71.0 in. |
Table 2. Electrical| Electrical characteristics |
50961 |
50962 |
| kVA3 |
0.389 - 1.100 |
0.389 - 1.100 |
| Rated voltage and frequency |
200 - 240 V ac at 50 - 60 plus
or minus 0.5 Hz |
200 - 240 V ac at 50 -
60 plus or minus 0.5 Hz |
| Thermal output (maximum)3 |
1075 - 3379 Btu/hr |
1075 - 3379 Btu/hr |
| Power requirements (maximum)3 |
315 - 990 W |
315 - 990 W |
| Power factor |
0.95 |
0.95 |
| Inrush current |
50 A |
50 A |
| Leakage current (maximum) |
3.5 mA |
3.5 mA |
| Phase |
1 |
1 |
Table 3. Temperature requirements| Operating |
Nonoperating |
| 10 - 38°C (50 - 100.4°F) |
1 - 60°C (33.8 - 140°F) |
Table 4. Environment requirements| Properties |
Operating |
Non-Operating |
| Noncondensing Humidity |
8 - 80% |
8 - 80% |
| Wet bulb temperature |
23°C (73.4°F) |
27°C (80.6°F) |
Table 5. Maximum altitude| 3048 m (10 000 ft) |
Table 6. Noise emissions1| Properties |
Operating |
Idle |
| LWAd Category 2E, General
business |
7.0 bels |
6.9 bels |
| LpAm (1-meter bystander) |
52 dB |
52 dB |
Table 7. Service clearances| Dimensions |
Front |
Back |
Sides |
Top |
| Metric |
762 mm |
762 mm |
762 mm |
762 mm |
| English |
30 in. |
30 in. |
30 in. |
30 in. |
Table 8. NotesNotes:
- Because the 5296 1.8
m I/O rack consists of two 5096 expansion units,
electrical requirements for each 5096 need to be planned
for individually. Hence, the (1) and (2) represent the specifications
for each 5096.
The 5096 requires
the appropriate receptacle for the power cord included with each 5096
- The usable length of the power cord for the top/upper 5096 is
reduced by 4 ft (1.2 m) because of the routing inside the 1.8 m enclosure.
Therefore, a 14 ft (4.3 m) cord results in a usable length of 10
ft (3 m), and a 9 ft (2.7 m) cord results in a usable length of 5
ft (1.5 m).
- Each 5096 can
have 45 disk drives installed. Each disk drive that is installed adds
15 W, 0.0158 kVa to the power. The range of power represents configurations
from no disk drives to 45 disk drives.
|
For information about floor loading, contact your IBM® service
or Installation Planning representative. Because the thickness of
the covers are negligible, the height, width, and depth of the overall
dimensions might be used in floor loading calculations.