5296 1.8 m I/O rack

Hardware specifications provide detailed information for your rack, including dimensions, electrical, power, temperature, environment, and service clearances.

Table 1. Dimensions
Dimensions Maximum configuration weight Width Depth Height
Metric 726 kg 650 mm 1020 mm 1800 mm
English 1600 lb 25.5 in. 40.1 in. 71.0 in.
Table 2. Electrical
Electrical characteristics 50961 50962
kVA3 0.389 - 1.100 0.389 - 1.100
Rated voltage and frequency  200 - 240 V ac at 50 - 60 plus or minus 0.5 Hz 200 - 240 V ac at 50 - 60 plus or minus 0.5 Hz
Thermal output (maximum)3 1075 - 3379 Btu/hr 1075 - 3379 Btu/hr
Power requirements (maximum)3   315 - 990 W 315 - 990 W
Power factor   0.95 0.95
Inrush current 50 A 50 A
Leakage current (maximum)  3.5 mA 3.5 mA
Phase 1 1
Table 3. Temperature requirements
Operating Nonoperating
10 - 38°C (50 - 100.4°F) 1 - 60°C (33.8 - 140°F)
Table 4. Environment requirements
Properties Operating Non-Operating
Noncondensing Humidity   8 - 80% 8 - 80%
Wet bulb temperature   23°C (73.4°F) 27°C (80.6°F)
Table 5. Maximum altitude
3048 m (10 000 ft)
Table 6. Noise emissions1
Properties Operating Idle
LWAd Category 2E, General business 7.0 bels 6.9 bels
LpAm (1-meter bystander) 52 dB 52 dB
Table 7. Service clearances
Dimensions Front Back Sides Top
Metric 762 mm 762 mm 762 mm 762 mm
English 30 in. 30 in. 30 in. 30 in.
Table 8. Notes
Notes:
  1. Because the 5296 1.8 m I/O rack consists of two 5096 expansion units, electrical requirements for each 5096 need to be planned for individually. Hence, the (1) and (2) represent the specifications for each 5096. The 5096 requires the appropriate receptacle for the power cord included with each 5096
  2. The usable length of the power cord for the top/upper 5096 is reduced by 4 ft (1.2 m) because of the routing inside the 1.8 m enclosure. Therefore, a 14 ft (4.3 m) cord results in a usable length of 10 ft (3 m), and a 9 ft (2.7 m) cord results in a usable length of 5 ft (1.5 m).
  3. Each 5096 can have 45 disk drives installed. Each disk drive that is installed adds 15 W, 0.0158 kVa to the power. The range of power represents configurations from no disk drives to 45 disk drives.

For information about floor loading, contact your IBM® service or Installation Planning representative. Because the thickness of the covers are negligible, the height, width, and depth of the overall dimensions might be used in floor loading calculations.


Send feedback | Rate this page