Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.
This product meets the technical requirements of IEC 61000-3-3.
Models 9406-870 and 9406-890 have some additional information that is important during planning.
Pictured is the model 9406-870 or 9406-890 server with the 9094 expansion unit |
![]() |
|||
| Dimensions | Width | Depth | Height | |
| Metric (mm) | 785 | 1494 | 2025 | |
| English (in.) | 30.91 | 58.83 | 79.72 | |
| Depth without covers | 1173.5 mm (46.2 in) | |||
| Standard shipping crate | 940 mm (37 in.) | 1422 mm (56 in.) | 2337 mm (92 in.) | |
| Reduced height shipping crate | 940 mm (37 in. | 1422 mm (56 in.) | 2032 mm (80 in.) | |
| Height reduction feature 0126 System frame is included in two pieces to be fully assembled at customer location. | 1.65 m (65 in) | |||
| Maximum configuration weight | 800 kg (1758 lb.) | |||
| Electrical and thermal | ||||
| kVA (maximum) 8-way (9406-870) 16-way (9406-870) 24-way (9406-890) 32-way (9406-890) |
6.315 6.315 8.201 10.099 |
|||
| Rated voltage at 50-60 plus or minus 0.5 Hz (3-phase)3, 4 | 200-240 V ac 380-415 V ac 480 V ac |
|||
| Rated current (amps per phase) 200-240 V ac 380-415 V ac 480 V ac |
45 A 25 A 20 A |
|||
| Thermal output (maximum) 8-way (9406-870) 16-way (9406-870) 24-way (9406-890) 32-way (9406-890) |
20.478 kBtu/hr 20.478 kBtu/hr 26.591 kBtu/hr 32.744 kBtu/hr |
|||
| Power requirements maximum 8-way (9406-870) 16-way (9406-870) 24-way (9406-890) 32-way (9406-890) |
6000 W 6000 W 7791 W 9594 W |
|||
| Power factor | 0.95 | |||
| Frequency (Hertz) | 50 to 60 | |||
| Inrush current3 | 163 A | |||
| Leakage current | 42 mA | |||
| Phase | 3 | |||
| Power cord feature 200-240 V ac 380-415 V ac 480 V ac | ||||
| Power cord length | 4.3 m (14 ft.) or 1.8 m (6 ft.) (U.S. only) | |||
| Compatible receptacle 200-240 V ac 380-415 V ac 480 V ac |
IEC 309, 60A 460R9W Not specified, electrician installed IEC 309, 30A 430R7W |
|||
| Plug type (NoIBM plug type available) 200-240 V ac 380-415 V ac 480 V ac |
IEC 309, 60A 460P9W Not specified IEC 309, 30A 430P7W |
|||
| Temperature requirements | ||||
| Operating | 10 degrees to 32 degrees C (50 degrees to 89.6 degrees F) | |||
| Nonoperating | 10 degrees to 43 degrees C (50 degrees to 109.4 degrees F) | |||
| Storage | 1 degrees to 60 degrees C (33.8 degrees to 140 degrees F) | |||
| Shipping | -40 degrees to 60 degrees C (-40 degrees to 140 degrees F) | |||
| Environment requirements | Operating | Non operating | Storage | Shipping |
| Noncondensing humidity | 8 to 80% | 8 to 100% | 5 to 80% | 5 to 100% |
| Wet bulb temperature | 23 degrees C (73.4 degrees F) | 27 degrees C (80.6 degrees F) | 29 degrees C (84.2 degrees F) | 29 degrees C (84.2 degrees F) |
| Maximum altitude | 2134 m (7000 ft.) | |||
| Noise emissions1 | Operating | Idle | ||
| LWAd | 7.2 bels | 7.2 bels | ||
| LpAm (1-meter bystander) | 54 dB | 54 dB | ||
| Service clearances | |||
| Front | Back | Sides * | Top * |
| 1143 mm | 914 mm | 762 mm | 762 mm |
| 45 in. | 36 in. | 30 in. | 30 in. |
Note:
|
|||
* Side and top clearances are optional when operating if the building floor loading specifications are met.