Model 9406-830 and SB2 server specifications

Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.

Use the following specifications to plan for your server.

Table 1. Server specifications

Pictured is model 9406-830 or model SB2 including the 9074 I/O enclosure.

Both models include the 9074 I/O enclosure.

The 5074, 5078, or 5079 PCI expansion unit is available with model 9406-830 or model SB2.

Dimensions for both models are identical and include the 9074 I/O enclosure.

9406-830/SB2
Dimensions Width Depth Height
Metric 483 mm 1080 mm 1270 mm
English 19.0 in. 42.5 in. 50.0 in.
 
Maximum configuration weight 400 kg (881.5 lb.)
Electrical 
kVA (maximum) 1.684
Rated voltage and frequency3 200-240 V ac at 50-60 plus or minus 0.5 Hz
Thermal output (maximum) 5461 Btu/hr
Power requirements (maximum) 1600 W
Power factor 0.95
Inrush current 80 A
Leakage current (maximum) 3.5 mA
Phase 1
Compatible plug types 5, 10, 11, 18, 22, 23, 25, 2932, 34, 35, 46 (P+N+G)[16A], 54
Power cord length 1.8 m (6 ft.)(U.S. only) or 4.3 m (14 ft.)
High-speed link (HSL) cable requirements
Temperature requirements
Operating 10 degrees to 38 degrees C (50 degrees to 100.4 degrees F)
Nonoperating 1 degrees to 60 degrees C (33.8 degrees to 140 degrees F)
Environment requirements Operating Nonoperating
Noncondensing humidity 8 to 80% 8 to 80%
Wet bulb temperature 22.8 degrees C (73 degrees F) 27 degrees C (80.6 degrees F)
Maximum altitude 3048 m (10000 ft.)
Noise emissions1 Operating Idle
LWAd (Category 2D, General busness) 6.7 bels 6.7 bels
LpAm (1-meter bystander) 50 dB 49 dB
Service clearances
Front Back Sides2 Top2
762 mm 762 mm 762 mm 762 mm
30 in. 30 in. 30 in. 30 in.

Notes:

  1. For a description of noise emission values, see the Acoustics chapter of the Site Preparation and Physical Planning Guide, SA76-0103.
  2. Side and top clearances are optional when operating.
  3. The power supplies automatically accept any voltage with the published rated voltage range. If dual power supplies are installed and operating, the power supplies draw approximately equal current from the utility (mains) and provide approximately equal current to the load.