Model 9406-520, 9111-520, 9405-520, 9111-285, 9131-52A, 9406-525, 9407-515 server specifications

Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.

Use the following specifications to plan for your server.

Table 1. Server specifications5

Plan views

Top down view

ASHRAE declarations

Rack-mounted drawer
Dimensions Width Depth Height EIA units1 Weight
Metric 437 mm 584 mm 178 mm 4 43 kg
English 17.20 in. 23 in. 7 in. 95 lb.
Desk-side server
Dimensions Width Depth Height Weight
Metric 201 mm

630 mm (without rear cover

706 mm (with 6587 rear cover)

533 mm 43 kg
English 7.9 in.

23 in. (without rear cover)

27.8 in. (with 6587 rear cover)

21 in. 95 lb.
Rack-mounted drawer
Shipping Dimensions Width Depth Height Weight
Metric 630 mm 933 mm 584 mm 53 kg
English 24.80 in. 36.75 in. 23 in. 117 lb.
Rack-mounted drawer (China)
Shipping Dimensions Width Depth Height Weight
Metric 679 mm 978 mm 610 mm 53 kg
English 26.75 in. 38.50 in. 24 in. 117 lb.
Desk-side server
Shipping Dimensions Width Depth Height Weight
Metric 584 mm 880 mm 813 mm 50 kg
English 23 in. 34.65 in. 32 in. 110 lb.
Desk-side server (China)
Shipping Dimensions Width Depth Height Weight
Metric 616 mm 904 mm 832 mm 63 kg
English 24.25 in. 35.60 in. 32.75 in. 138 lb.

Feature code for drawer mounted in rack

Optional power distribution unit (PDU), 0551 rack, 7014-T00, 7014-T42, 0553, Start of change0555End of change racks

7884 (9406-520, 9405-520, 9406-525, 9407-515)

0229 (9111-520)

Electrical
kVA (maximum) 0.789
Rated voltage and frequency6 100 - 127/200 - 240V ac at 50/60 plus or minus 0.5 Hz
Thermal output (maximum) 2560 Btu/hr
Maximum power consumption 750 W
Power factor 0.95
Inrush current (maximum) 88 A
Leakage current (maximum) 1.2 mA
Phase 1
Compatible plug types 2, 4, 5, 6, 10, 18, 19, 22, 23, 24, 25, 32, 34, 62, 64, 66, 69, 70, 75, 76
Dual power feature code 5159
Branch circuit breaker 20 A (maximum)
Power cord length

2.8 m (9 ft.) - except United States

1.8 m (6 ft.) - United States

Environment requirements
Recommended operating temperature2 5 degrees to 35 degrees C (41 degrees to 95 degrees F)
Nonoperating temperature 5 degrees to 45 degrees C (41 degrees to 113 degrees F)
Shipping temperature -40 degrees to 60 degrees C (-40 degrees to 140 degrees F)
Operating4 Nonoperating
Maximum dew point 28 degrees C (82.4 degrees F) 29 degrees C (84.2 degrees F)
Noncondensing humidity 8 to 80% 8 to 80%
Maximum altitude 3048 m (10000 ft.) 3048 m (10000 ft.)
Noise emissions3, 8, 9
Product description Declared A-weighted sound power level, LWad (B) Declared A-weighted sound pressure level, LpAm (dB)
Operating Idle Operating Idle
9111-285 workstation 5.0 5.0 35 32
9131-52A, 9406-520, 9111-520, and 9405-520 desk side server with two power supplies, eight hard drives and acoustic package 5.7 5.6 40 39
9131-52A, 9406-520, 9111-520, and 9405-520 desk side server with two power supplies and eight hard drives 6.1 5.9 44 41
9406-520 and 9111-520 rack-mounted server 6.0 5.8 43 42
Service clearances
Clearances Front Back Left or right Top
Operating 762 mm (30 in.) 762 mm (30 in.)  
Nonoperating 762 mm (30 in.) 762 mm (30 in.) 762 mm (30 in.) 762 mm (30 in.)
Seismic considerations
Data communications
Electromagnetic compatibility compliance: This server meets the following electromagnetic compatibility specifications: FCC (CFR 47, Part 15); VCCI; CISPR-22; 89/336/EEC; BSMI (A2/NZS 3548:1995); C-Tick; ICES/NMB-003; Korean EMI/EMC (MIC Notice 2000–94, Notice 2000–72); People's Republic of China Commodity Inspection Law
Safety compliance: This server is designed and certified to meet the following safety standards: UL 60950; CAN/CSA C22.2 No. 60950–00; EN 60950; IEC 60950 including all National Differences
Note:
  1. See 0551, 0553, 7014, or Start of change0555End of change rack configurations for typical configurations when the 0551, 0553, 7014, or Start of change0555End of change rack is populated with various server models.
  2. Class 3 product as defined in ASHRAE Thermal Guidelines for Data Processing Environments. The allowable operating range is 5 degrees to 35 degrees C (41 degrees to 95 degrees F). See the Temperature and humidity design chapter of the Site Preparation and Physical Planning Guide, SA76-0103, for more information.
  3. For a description of noise emission values, see the Acoustics chapter of the Site Preparation and Physical Planning Guide, SA76-0103.
  4. All Model 520 disk bays should be filled when the unit is shipped from IBM® with either disk drives or slot fillers, but if a disk is removed, refill the disk slot with either another disk drive or a disk slot filler. Filling the disk drive slot will help ensure proper airflow for cooling and help maintain optimal EMI compliance. Ordering feature 6598 results in four additional disk slot fillers being shipped.
  5. The model 9405-520 is available as a deskside model only.
  6. The power supplies automatically accept any voltage with the published rated voltage range. If dual power supplies are installed and operating, the power supplies draw approximately equal current from the utility (mains) and provide approximately equal current to the load.
  7. The model 9111-2858, is only available as a desk-side model.
  8. When a tape drive is installed, using the acoustic cover feature will reduce the noise emissions when the tape drive is in use.
  9. All measurements made in conformance with ISO 7779 and declared in conformance with ISO 9296.

Special Hardware Management Console considerations

When the 9406-520, 9111-520, 9405-520, 9111-285, 9131-52A, 9406-525, 9407-515 servers are managed by a Hardware Management Console (HMC), the console must be provided within the same room and within 8 m (26 ft.) of the server.

Note: As an alternative to the local HMC requirement, it is acceptable for you to provide a supported device (such as, a PC), with connectivity and authority to operate through a remotely attached HMC. This local device must be in the same room and within 8 m (26 ft.) of your server, and provide functional capability equivalent to the HMC that it replaces and that is needed by the service representative to service the system.