Hardware specifications provide detailed information for your rack, including dimensions, electrical, power, temperature, environment, and service clearances.
| Dimensions | Height | Width | Depth |
| Metric | 1800 mm | 650 mm | 1020 mm |
| English | 71.0 in. | 25.5 in. | 40.1 in. |
| Maximum configuration weight | 726 kg (1600 lb.) | ||
| Electrical(1, 2) | 50961 | 50962 | |
| kVA3 | 0.389 - 1.100 | 0.389 - 1.100 | |
| Rated voltage and frequency | 200-240 V ac at 50-60 plus or minus 0.5 Hz | 200-240 V ac at 50-60 plus or minus 0.5 Hz | |
| Thermal output (maximum)3 | 1075 - 3379 Btu/hr | 1075 - 3379 Btu/hr | |
| Power requirements (maximum)3 | 315 - 990 W | 315 - 990 W | |
| Power factor | 0.95 | 0.95 | |
| Inrush current | 50 A | 50 A | |
| Leakage current (maximum) | 3.5 mA | 3.5 mA | |
| Phase | 1 | 1 | |
| Plug type (Canada and U.S.) | Type 10 lower unit cord feature 1453 (6 ft. 14F1549) and upper unit cord feature 1458 (9 ft. 12J5119, with only 6 ft. usable length), Type 34 lower unit cord feature 1455 (6 ft. 14F1551) and upper unit cord feature 1459 (9 ft. 55H6644, with only 6 ft. usable length), or Type 5 lower unit cord feature 1451 (6 ft. 14F1547) and upper unit cord feature 1457 (9 ft. 12J5120, with only 6 ft. usable length) |
||
| Power cord length(1, 2) (U.S. only) | 1.8 m (6 ft.) 2.7 m (9 ft.) | 1.8 m (6 ft.) 2.7 m (9 ft.) | |
| Temperature requirements | |||
| Operating | 10 degrees to 38 degrees C (50 degrees to 100.4 degrees F) | ||
| Nonoperating | 1 degrees to 60 degrees C (33.8 degrees to 140 degrees F) | ||
| Environment requirements | Operating | Nonoperating | |
| Noncondensing humidity | 8% to 80% | 8% to 80% | |
| Wet bulb temperature | 23 degrees C (73.4 degrees F) | 27 degrees C (80.6 degrees F) | |
| Maximum altitude | 3048 m (10000 ft.) | ||
| Noise emissions | Operating | Idle | |
| LWAd Category 2E, General business | 7.0 bels | 6.9 bels | |
| <LpA>m | 52 dB | 52 dB | |
| Service clearances | |||
| Front | Back | Sides | Top |
| 762 mm | 762 mm | 762 mm | 762 mm |
| 30 in. | 30 in. | 30 in. | 30 in. |
Note:
|
|||
For information about floor loading, contact your IBM® service or Installation Planning representative. Because the thickness of the covers are negligible, the height, width, and depth of the overall dimensions may be used in floor loading calculations.