5074 expansion unit or 9079 expansion unit with 5078 expansion unit

Hardware specifications provide detailed information for your expansion unit, including dimensions, electrical, power, temperature, environment, and service clearances.

Table 1. Hardware specifications

Pictured is the 5074 expansion unit or 9079 expansion unit with 5078 expansion unit.

5074
Dimensions Width Depth Height
Metric 485 mm 1075 mm 1110 mm
English 19.1 in. 42.3 in. 43.8 in.
 
Maximum configuration weight 418 kg (922 lb.)
Electrical
kVA (maximum) 1.470
Rated voltage frequency 200-240 V ac at 50-60 plus or minus 0.5 Hz
Thermal Output (maximum) 4573 Btu/hr
Power requirements (maximum) 1340 W
Power factor 0.91
Inrush current 90 A
Leakage current (maximum) 3.5 mA
Phase 1
Plug type (Canada and U.S.) 10, 34, or 5
Power cord length 1.8 m (6 ft. ) (U.S. only) or 4.3 m (14 ft. )
Temperature requirements
Operating 10 degrees to 38 degrees C (50 degrees to 100.4 degrees F)
Non operating 1 degrees to 60 degrees C (33.8 degrees to 140 degrees F)
Environment requirements Operating Nonoperating
Noncondensing humidity 8 to 80% 8 to 80%
Wet bulb temperature 23 degrees C (73.4 degrees F) 27 degrees C (80.6 degrees F)
Maximum altitude 3048 m (10000 ft.)
Noise emissions1
5074 Operating Idle
LWAd 6.7 bels 6.6 bels
LpAm (1-meter bystander) 48 dB 48 dB
5074 with 5078 expansion unit Operating Idle
LWAd 6.9 bels 6.8 bels
LpAm (1-meter bystander) 52 dB 51 dB
Service clearances
Front Back Sides2 Top2
762 mm 762 mm 762 mm 762 mm
30 in. 30 in. 30 in. 30 in.

Notes:

  1. For a description of noise emission values, see the Acoustics chapter of the Site Preparation and Physical Planning Guide, SA76-0103.
  2. Side and top clearances are optional during operation.