Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.
Use the following specifications to plan for your server.
| Server specifications | |||||
|---|---|---|---|---|---|
| Rack-mounted drawer | |||||
| Dimensions | Width | Depth | Height | EIA Units3 | Weight |
| Metric | 440 mm | 710 mm | 43 mm | 1 | 17 kg |
| English | 17.3 in. | 28.0 in. | 1.7 in. | 37 lb. | |
| Rack-mounted drawer | |||||
| Shipping dimensions | Width | Depth | Height | Weight | |
| Metric | 635 mm | 851 mm | 330 mm | 20 kg | |
| English | 25.0 in. | 33.5 in. | 13.0 in. | 43 lb. | |
| Rack-mounted drawer (China) | |||||
| Shipping dimensions | Width | Depth | Height | Weight | |
| Metric | 610 mm | 1016 mm | 445 mm | 27 kg | |
| English | 24.0 in. | 40 in. | 17.5 in. | 60 lb. | |
| Feature code for drawer mounted in rack Power
distribution Unit (PDU), 0551, 7014-T00, 7014-T42 and 0553 , |
0259 | ||||
| Electrical | |||||
| kVA (maximum) | 0.526 | ||||
| Rated voltage, rated amps, and frequency4 | 9115-505 | 100-127 V ac (12 A) to 200-240 V ac (10 A) at 50 to 60 plus or minus 0.5 Hz |
|||
| Thermal output (maximum) | 1707 Btu/hr | ||||
| Maximum power consumption | 500 W | ||||
| Power factor | 0.95 | ||||
| Inrush current (maximum) | 75 A | ||||
| Leakage current (maximum) | 1.2 mA | ||||
| Phase | 1 | ||||
| Compatible plug types | 2, 4, 5, 6, 18, 19, 22, 23, 24, 25, 2632, 57, 59, 62 , 66, 69, 70, 73, 75, 76 | ||||
| Dual power feature code | 7958 (quantity 2) | ||||
| Branch circuit breaker | 20 A (maximum) | ||||
| Power cord length | 2.8 m (9 ft.) - except United States 1.8 m (6 ft.) - United States |
||||
| Environment requirements | |||||
| Recommended operating temperature2 | 5 degrees to 35 degrees C (41 degrees to 95 degrees F) | ||||
| Nonoperating temperature | 5 degrees to 45 degrees C (41 degrees to 113 degrees F) | ||||
| Shipping temperature | -40 degrees to 60 degrees C (-40 degrees to degrees 140 F) | ||||
| Operating | Nonoperating | ||||
| Maximum dew point | 28 degrees C (82.4 degrees F) | 29 degrees C (84.2 degrees F) | |||
| Noncondensing humidity | 8 to 80% | 8 to 80% | |||
| Maximum altitude | 3048 m (10000 ft.) | 3048 m (10000 ft.) | |||
| Noise emissions1, 5 | |||||
| Product description | Declared A-weighted sound power level, LWad (B) | Declared A-weighted sound pressure level, LpAm (dB) | |||
| Operating | Idle | Operating | Idle | ||
| 9115-505 with two hard drives and two power supplies | 6.8 | 6.8 | 52 | 52 | |
| 9115-505 with acoustic door (feature code 6248 or 6249) with two hard drives and two power supplies | 6.2 | 6.2 | 44 | 44 | |
| Service clearances | |||||
| Clearances | Front | Back | Left or right | Top | |
| Operating | 762 mm (30 in.) | 762 mm (30 in.) | |||
| Nonoperating | 762 mm (30 in.) | 762 mm (30 in.) | 762 mm (30 in.) | 762 mm (30 in.) | |
| Seismic considerations | |||||
| Data communications | |||||
| Electromagnetic compatibility compliance: This server meets the following electromagnetic compatibility specifications: FCC (CFR 47, Part 15); VCCI; CISPR-22; 89/336/EEC; BSMI (A2/NZS 3548:1995); C-Tick; ICES/NMB-003; Korean EMI/EMC (MIC Notice 2000–94, Notice 2000–72); People's Republic of China Commodity Inspection Law | |||||
| Safety compliance: This server is designed and certified to meet the following safety standards: UL 60950; CAN/CSA C22.2 No. 60950–00; EN 60950; IEC 60950 including all National Differences | |||||
Note:
|
|||||