Model 0550 and 9406-830 rack
Rack specifications provide detailed information for your rack, including dimensions, electrical, power, temperature, environment, and service clearances.
Figure 1. 0550 rack

Figure 2. 0550 rack configuration

| Maximum configuration weight | Width | Depth | Height | EIA units |
|---|---|---|---|---|
| 644 kg (1417 lb) | 650 mm (25.5 in.) | 1020 mm (40.0 in. ) | 1800 mm (71.0 in. ) | 36 |
| The 1.8 meter rack has 10 EIA units of space remaining. This space will be filled with a 5 EIA filler panel, a 3 EIA filler panel, and two of the 1 EIA filler panels. Because the rack does not have power distribution, the model 9406-830 rack requires a power cord of sufficient length to reach the receptacle. The power cord for model 9406-830 rack must be used to determine the appropriate receptacle. | ||||
| Electrical characteristics | Properties |
|---|---|
| kVA (maximum) | 1.684 |
| Rated voltage and frequency | 200 - 240 V ac at 50 - 60 plus or minus 0.5 Hz |
| Thermal output (maximum) | 5461 Btu/hr |
| Power requirements (maximum) | 1600 W |
| Power factor | 0.95 |
| Inrush current | 80 A |
| Leakage current (maximum) | 3.5 mA |
| Phase | 1 |
| Front | Back | Sides | Top |
|---|---|---|---|
| 762 mm (30 in.) | 762 mm (30 in.) | 762 mm (30 in.) | 762 mm (30 in.) |
| Side and top clearances are optional when operating. | |||
| Feature Code | Top rack specify | Bottom rack specify | PDU support | Power cords |
|---|---|---|---|---|
| 05501 | None | None | 0 to 42 | Model 9406-8303, PDU |
1 Ten EIA units of space not managed by the configurator. 2 Feature codes 5160, 5161, and 5162. 3 Model 9406-830 does not plug into a power distribution unit. |
||||