Installing the PDU, PDU+, or Intelligent Switched PDU in the side of a rack

Learn how to install the power distribution unit (PDU), power distribution unit plus (PDU+), or Intelligent Switched PDU vertically in the side of a rack.

Tip: Removing the rack doors and side panels makes installing the PDU easier.
To install the PDU model in a single EIA vertical mounting space in the side of the rack, complete the following steps:
  1. Read the Rack safety notices.
  2. Choose one of the following options to install your PDU model:
    • To install the PDU or Intelligent Switched PDU, go to step 5.
    • To install the PDU+, continue with step 3.
  3. Align the vertical-mounting brackets (A) to the front of the PDU+. Make sure that you attach the brackets so that the power outlets face the rear of the rack.
    Figure 1. Aligning the vertical-mounting brackets to the front of the PDU+
    Aligning the vertical-mounting brackets to the front of the PDU+.
  4. Attach the brackets (A) to the PDU+ with two M3x5 screws (B) per bracket. Use screws that were provided with the rack mounting kit.
  5. Attach nut clips (A) to the four locations on the rack mounting flanges where you want to attach the PDU model. Use nut clips that were provided with the rack mounting kit. See the following figure.
    Figure 2. Attaching nut clips to the rack mounting flanges from the rear of the rack
    Attaching nut clips to the rack mounting flanges.
  6. Align the PDU model with the opening in the side of the rack. Then, while you hold the PDU model in place, attach the brackets to the nut clips in the rack mounting flanges with four M5 screws (A) as shown in the following figure. Use screws that were provided with the rack mounting kit.
    Figure 3. Aligning the PDU+ with the opening in the side of the rack, seen from the rear of the rack
    Aligning the PDU+ with the opening in the side of the rack.
    Attention: You must ensure that the main input power is disconnected from the power source before you connect or disconnect the input power cord from the PDU model.
  7. If the PDU model was provided with a detached power cord, connect the power cord now. Align the connector on the power cord (A) that was provided with the PDU model with the connector on the front of the unit (A), turning as necessary for key alignment. Then, turn the connector twist-lock (B) clockwise until it locks into place.
    Figure 4. Aligning the connector on the power cord with the PDU model
    Aligning the connector on the power cord with the PDU model.
  8. Route the power cord from the PDU model toward the rack side braces. Then, route the power cord along a side brace toward the rear of the rack and secure the power cord with the cable straps that are provided with the PDU model.
  9. Route the power cord toward a dedicated power source. Use the provided cable straps to secure the power cord along the way. Use the openings in the rack, if the power cord must exit the rack to connect to a power source.
    Attention: To prevent damage to a power device and other connected devices, always connect the power device to an authorized power source for that device.
  10. Connect the power cord to a properly wired and grounded dedicated power source. Then, connect the servers or rack PDU in the rack to the power outlets on the PDU model.
  11. Route all of the other power cables neatly, and secure the power cables with cable straps.
  12. If you removed the side covers or doors, reinstall them.

Installing the PDU, PDU+, or Intelligent Switched PDU horizontally in a rack

Learn how to install the power distribution unit (PDU), power distribution unit plus (PDU+), or Intelligent Switched PDU horizontally in the side of a rack.

Tip: Removing the rack doors and side panels might make installing the PDU easier.
To install the PDU model in a single EIA horizontal mounting space in the rack, complete the following steps:
  1. Read the Rack safety notices.
  2. Identify an open mounting space that is the size of a single EIA in the rack where you are installing the PDU model. Attach the nut clips to the top and bottom holes of the EIA, on each side of the rack. Use the nut clips that were provided with the rack mounting kit.
  3. If you are installing a PDU, continue with the next step. Otherwise, for a PDU+, go to step 6. For the Intelligent Switched PDU, go to step 7.
  4. Align the PDU with the opening of the rack. Then, while you hold the PDU in place, attach the PDU mounting brackets to the nut clips in the rack with four M6 screws. Use screws that were provided with the rack mounting kit.
  5. Go to step 15 for power cord attachment.
  6. Align the vertical-mounting brackets (A) to the front of the PDU+ as shown in the following figure. Make sure that you attach the brackets so that the power outlets face the rear of the rack.
    Figure 5. Aligning the vertical-mounting brackets to the front of the PDU+
    Aligning the vertical-mounting brackets to the front of the PDU+ or Intelligent Switched PDU.
  7. Attach the brackets (A) to the PDU+ or Intelligent Switched PDU with two M3x5 screws (B) per bracket. Use screws that were provided with the rack mounting kit.
  8. If you are installing the PDU or PDU+ long mounting brackets, align the long mounting brackets (A) with the holes in the rear of the PDU, and attach the brackets to the PDU model with two M3 pan-head screws (B) with captive lock washers per bracket. Use screws that were provided with the rack mounting kit.
    Figure 6. Attaching the long mounting brackets to the PDU and PDU+
    Attaching the long mounting brackets.
    If you are installing the Intelligent Switched PDU adjustable mounting rails, complete the following tasks:
    1. Assemble the adjustable mounting rail by using the four screws that are included with the mounting kit.
    2. Attach the adjustable mounting rails to each side of the PDU chassis by using the six screws that are included with the mounting kit.
  9. Identify an open mounting space that is the size of a single EIA in the rack where you are installing the PDU model. At the rear of the rack, attach nut clips to the top and bottom holes of the EIA on each side of the rack. Use nut clips that were provided with the rack mounting kit.
    Note: If your rack has square mounting holes, attach cage nuts instead of nut clips to the specified EIA locations. Use cage nuts that were provided with the rack mounting kit.
  10. Hold the PDU model at a slight angle and carefully insert it into a mounting space that is a single EIA unit within the rack cabinet. Pushing in slightly on both of the long mounting brackets helps clear the brackets from the rack flanges.
  11. Align the end of the PDU model with the short mounting brackets with the outside of the rack flanges. Use two M6 screws (A) if cage nuts are used or M5 screws if nut clips are used per bracket to attach the brackets to the nut clips or cage nuts on the rack flanges. Use screws that were provided with the rack mounting kit.
    Figure 7. Attaching the front of the PDU+ or Intelligent Switched PDU in the rack
    Attaching the front of the PDU+ or Intelligent Switched PDU in the rack.
  12. If the side covers are installed, continue with step 13. If you removed the side covers, go to step 14.
  13. Secure the long mounting brackets and the blank filler panel (A) to the rack cabinet by completing the following steps:
    1. Adjust the long mounting brackets to fit the depth of the rack cabinet.
    2. Place a mark on both rails at the rear of the PDU, PDU+, or Intelligent Switched PDU.
    3. Remove the two M6 screws (A) if cage nuts are used, or M5 screws that secure the PDU, PDU+, or Intelligent Switched PDU to the rack flanges.
    4. Carefully remove the PDU, PDU+, or Intelligent Switched PDU from the rack frame.
    5. Position the marks on the rails so that they are at the rear of the PDU, PDU+, or Intelligent Switched PDU.
    6. Tighten the M3 pan-head screws that secure the long mounting brackets to the PDU, PDU+, or Intelligent Switched PDU model.
    7. Hold the PDU, PDU+, or Intelligent Switched PDU model at a slight angle and carefully insert it into a mounting space that is a single EIA unit within the rack cabinet. Pushing in slightly on both of the long mounting brackets helps clear the brackets from the rack flanges.
    8. Align the end of the PDU, PDU+, or Intelligent Switched PDU model with the short mounting brackets with the outside of the rack flanges. Ensure that the rails align properly with the front rack flanges. If not, mark and readjust the mounting rails length by removing the PDU, PDU+, or Intelligent Switched PDU and repeating steps 13.b through 13.g. Use two M6 screws (A) if cage nuts are used or M5 screws if nut clips are used per bracket to attach the brackets to the nut clips or cage nuts on the rear rack flanges.
    9. Make sure that the long mounting brackets are aligned with the inside of the rack flanges.
    10. Align the blank filler panel (A) on the outside of the rack flanges, as shown in Figure 7.
    11. Attach the filler panel to the rack flanges and then to the long mounting bracket with one M6 screw (B) per bracket. Use the screws that were provided with the rack mounting kit.
    12. Proceed with step 15.
  14. Secure the long mounting brackets and the blank filler panel (A) to the rack cabinet by completing the following steps:
    1. Adjust the long mounting brackets to fit the depth of the rack cabinet.
    2. Tighten the M3 pan-head screws that secure the long mounting brackets to the PDU, PDU+, or Intelligent Switched PDU model.
    3. Make sure that the long mounting brackets are aligned with the inside of the rack flanges.
    4. Align the blank filler panel (A) on the outside of the rack flanges.
    5. Attach the filler panel to the rack flanges and then to the long mounting bracket with one M6 screw (B) per bracket. Use screws that were provided with the rack mounting kit.
    Figure 8. Attaching the brackets and filler panel to the rack
    Attaching the brackets and filler panel to the rack.
  15. If the PDU, PDU+, or Intelligent Switched PDU model was provided with a detached power cord, connect the power cord now. Align the connector on the power cord (A) that was provided with the PDU, PDU+, or Intelligent Switched PDU model with the connector on the front of the unit (A), turning as necessary for key alignment. Then, turn the twist-lock (B) on the connector clockwise until it locks into place.
    Attention: Before you connect or disconnect the input power cord from the PDU, PDU+, or Intelligent Switched PDU model, you must disconnect the main input power.
    Figure 9. Aligning the connector on the power cord with the PDU, PDU+, or Intelligent Switched PDU model
    Aligning the connector on the power cord with the PDU, PDU+, or Intelligent Switched PDU model.
  16. Route the power cord from the PDU, PDU+, or Intelligent Switched PDU model toward the rack side braces. Route the power cord along a side brace toward the rear of the rack and secure the power cord with the cable straps that are provided with the PDU, PDU+, or Intelligent Switched PDU.
  17. Route the power cord toward a dedicated power source. Use the provided cable straps to secure the power cord along the way. If the power cord must exit the rack to connect to a power source, use the openings in the rack.
    Attention: To prevent damage to a power device and other connected devices, always connect the power device to an authorized power source for that device.
  18. Connect the power cord to a properly wired and grounded dedicated power source. Then, you can connect the servers or rack PDU, PDU+, or Intelligent Switched PDU in the rack to the power outlets on the PDU, PDU+, or Intelligent Switched PDU model.
  19. Route all of the other power cables neatly, and secure the power cables with cable straps.
  20. If the side covers or doors were removed, reinstall them.