If you choose to install ac mounting plates, you can follow
the procedure detailed in this section to perform this task. This
section also includes illustrations of the related hardware components
and shows how these components relate to each other.
If you do not want ac outlets installed on the rack,
go to Installing the ac outlet-mounting plate without ac outlets.
If you
want ac outlets installed on the front or rear ac outlet-mounting
plate, complete the following steps:
- Determine the number of ac outlets that you are installing.
- Confirm with your contractor that the number and location
of ac outlets to be installed are correct.
- Remove the blank filler plates from the ac outlet-mounting
plates for the number of ac outlets being installed.
- Install the ac outlets on the ac outlet-mounting plate.
- Install the ground lug in the ac outlet-mounting plate
using only one nut, as shown in the following illustration.
- Securely tighten the one nut on the ground lug.
- Locate the Y-shaped ground cable supplied with the mounting
plate.
Note: The remaining steps can be used to install
ac outlets on the front or the rear of the rack.
- Place the star washer onto the ground lug of the front
ac outlet-mounting plate.
- Place the lug on the long end of the ground cable onto
the ground lug.
- Place a ground lug nut onto the ground lug and securely
tighten it.
- Position the front ac outlet-mounting plate onto the rack
frame with the ground lug fully inserted through the mounting holes
in the rack.
- Route the cable under the rack.
- Place the star washer onto the ground lug of the rear ac
outlet-mounting plate.
- Place the lug on the short end of the ground cable onto
the ground lug.
- Place a ground lug nut onto the ground lug and securely
tighten it.
| 1 |
Ground cable lug |
7 |
Ground lug |
| 2 |
Star washer |
8 |
Ground connector (short end of ground cable) |
| 3 |
Front of rack |
9 |
"Y" end of ground cable |
| 4 |
Power cable from the power source |
10 |
Ground lug nut (quantity 2) |
| 5 |
Mounting plate |
11 |
Long end of ground cable |
| 6 |
Long end of ground cable |
12 |
Ground lug nut (quantity 2) |
Figure 1. Installing the ground lug
- Position the rear ac outlet-mounting plate onto the rack
frame with the ground lug fully inserted through the mounting holes
in the rack.
- Install the front ac outlet-mounting plate screws (stabilizer
mounting screws) into the mounting plate and through the mounting
holes in the rack. Securely tighten the screws.
| 1 |
Front or rear of rack (as applicable) |
4 |
Mounting plate |
| 2 |
Power cable from power source |
5 |
Allen wrench |
| 3 |
Button-head screw |
6 |
Long end of ground cable |
Figure 2. Installing the front mounting plate
- Connect the Y-shaped end of the ground cable to the rack
frame, either near the center in the back of the rack or to the ground
bus bar at the rear of the rack.
- Install the rear ac outlet-mounting plate screws (stabilizer
mounting screws) into the mounting plate and through the mounting
holes in the rack. Securely tighten the screws.
Note: The
bus bar might be located at either the top or bottom of the rack.
| 1 |
Bus bar mounting plate |
3 |
Hex screws (M5 x 20) (quantity 2) |
| 2 |
Lock washer (quantity 2) |
4 |
Ground bus bar |
Figure 3. Installing the back mounting plate