Power distribution units (PDUs) can be used with the 7014, 0551, 0553 and 0555 racks. The various configurations
and specifications are provided.
Power distribution unit
The following figure
shows the four vertical PDU locations in a rack.
Power distribution units (PDUs)
are required with 7014-T00, 7014-T42 IBM® racks and
optional with 7014-B42, 0553,
and 0555 racks,
except with a 0578 or 0588 expansion unit. If a PDU is not defaulted
or ordered, a power cord is provided with each individual rack-mounted
drawer for connection to a country-specific utility mains receptacle
or uninterruptible power supply. See the individual rack-mounted drawer
specifications for the appropriate power cords.
9188 or 7188 universal PDU
Table 1. 9188 universal PDU features| PDU Number |
Racks usage |
Supported power cords PDU to wall |
| 9188 universal PDU |
7014-T00 and 7014-T42 racks |
|
Table 2. 7188 universal PDU features| PDU Number |
Racks usage |
Supported power cords PDU to wall |
| 7188 universal PDU |
7014-T00, 7014-T42, 0551, 0553, and 0555 racks. |
|
The amperage rating of the PDU is either 16 A, 24 A, or
48 A, single phase or three-phase, depending on the power cord.
Note: All
power cords are 4.3 m (14 ft). For installation in Chicago, only 2.8
m (6 ft) of the 4.3 m (14 ft) power cord can extend beyond the perimeter
of the rack frame. If more than 2.8 m (6 ft) can exit the rack, retain
any additional cordage within the rack frame with hook-and-loop fastener
ties in the cable management space until 2.8 (6 ft) or less exits
the rack.
The PDU has twelve customer-usable IEC 320-C13
outlets rated at 200-240 V ac. There are six groups of two outlets
fed by six circuit breakers. Each outlet is rated up to 10 A (220
- 240 V ac) or 12 A (200 - 208 V ac), but each group of two outlets
is fed from one 20 A circuit breaker derated to 16 A.
5160 single phase PDU
Table 3. 5160 single phase PDU features| PDU Number |
Racks usage |
Supported power cords PDU to wall |
| 5160 single phase PDU |
0551, 0553, and 0555 IBM racks |
This is a hard wired power cord with a NEMA
L6-30P (30A, 250VAC). |
Typical rack and PDU configurations
See 0551, 0553, 7014,
and 0555 rack
configurations for typical configurations and PDUs when the
rack is populated with various server models.
Power distribution unit
plus specifications
The power distribution unit plus (PDU+) has power-monitoring
capabilities. The PDU+ is
an intelligent ac power distribution unit (PDU+) that monitors the
amount of power being used by the devices that are plugged into it.
The PDU+ provides
twelve C13 power outlets and receives power through a Souriau UTG
connector. It can be used in many geographies and for many applications
by varying the PDU-to-wall power cord, which must be ordered separately.
Each PDU+ requires
one PDU-to-wall power cord. When the PDU+ is connected
to a dedicated power source, it conforms to UL60950, CSA C22.2-60950,
EN-60950, and IEC-60950 standards.
5889 PDU+
Table 4. 5889
PDU+ features| PDU Number |
Racks usage |
Supported power cords PDU to wall |
| 5889 PDU+ |
7014 IBM racks |
|
Table 5. 5889 PDU+ specifications| Characteristics |
Properties |
| PDU number |
5889 |
| Height |
43.9 mm (1.73 in.) |
| Width |
447 mm (17.6 in.) |
| Depth |
350 mm (13.78 in.) |
| Additional clearance |
25 mm (0.98 in.) for circuit breakers |
| 3 mm (0.12 in.) for outlets |
| Weight (not including power cord) |
6.3 kg (13.8 lb) |
| Weight of power cord (approximate) |
5.4 kg (11.8 lb) |
| Operating temperature at 0 - 914 m (0 - 3000
ft) (room ambient) |
10 - 32°C (50 - 90°F) |
| Operating temperature at 914 - 2133 m (3000
- 7000 ft) (room ambient) |
10 - 35°C (50 - 95°F) |
| Operating humidity |
8 - 80% (noncondensing) |
| Localized air temperature in PDU |
60 °C (140°F) maximum |
| Rated frequency (all feature codes) |
50 - 60 Hz |
| Circuit breakers |
Six double-pole branch rated circuit breakers
rated at 20 A |
| Power outlet |
12 IEC 320-C13 outlets rated at 10 A (VDE) or
15 A (UL/CSA) |
7189 PDU+
Table 6. 7189
PDU+ features| PDU number |
Racks usage |
Supported power cords PDU to wall |
| 7189 PDU+ |
7014-B42 rack |
|
Table 7. 7189 PDU+ specifications| Characteristics |
Properties |
| PDU number |
7189 |
| Height |
43.9 mm (1.73 in.) |
| Width |
447 mm (17.6 in.) |
| Depth |
350 mm (13.78 in.) |
| Additional clearance |
25 mm (0.98 in.) for circuit breakers |
| 3 mm (0.12 in.) for outlets |
| Weight (not including power cord) |
6.3 kg (13.8 lb) |
| Weight of power cord (approximate) |
5.4 kg (11.8 lb) |
| Operating temperature at 0 - 914 m (0 - 3000
ft) (room ambient) |
10 - 32°C (50 - 90°F) |
| Operating temperature at 914 - 2133 m (3000
- 7000 ft) (room ambient) |
10 - 35°C (50 - 95°F) |
| Operating humidity |
8 - 80% (noncondensing) |
| Localized air temperature in PDU |
60°C (140°F) maximum |
| Rated frequency (all feature codes) |
50 - 60 Hz |
| Circuit breakers |
Six double-pole branch rated circuit breakers
rated at 20 A |
| Power outlet |
Six IEC 320-C19 outlets rated at 16 A (VDE)
or 20 A (UL/CSA) |
7196 PDU+
Table 8. 7196
PDU+ features| PDU Number |
Racks usage |
Supported power cords PDU to wall |
| 7196 PDU+ |
7014-B42 |
Fixed power cord with IEC 60309, 3P+E, 60
A plug |
Table 9. 7196 PDU+ specifications| Characteristics |
Properties |
| PDU number |
7196 |
| Height |
43.9 mm (1.73 in.) |
| Width |
447 mm (17.6 in.) |
| Depth |
350 mm (13.78 in.) |
| Additional clearance |
25 mm (0.98 in.) for circuit breakers |
| 3 mm (0.12 in.) for outlets |
| Weight (not including power cord) |
6.3 kg (13.8 lb) |
| Weight of power cord (approximate) |
5.4 kg (11.8 lb) |
| Operating temperature at 0 - 914 m (0 - 3000
ft) (room ambient) |
10 - 32°C (50 - 90°F) |
| Operating temperature at 914 - 2133 m (3000
- 7000 ft) (room ambient) |
10 - 35°C (50 - 95°F) |
| Operating humidity |
8 - 80% (noncondensing) |
| Localized air temperature in PDU |
60 °C (140 °F) maximum |
| Rated frequency (all feature codes) |
50 - 60 Hz |
| Circuit breakers |
Six double-pole branch rated circuit breakers
rated at 20 A |
| Power outlet |
Six IEC 320-C19 outlets rated at 16 A (VDE)
or 20 A (UL/CSA) |
7109 PDU+
Table 10. 7109
PDU+ features| PDU Number |
Racks usage |
Supported power cords PDU to wall |
| 7109 PDU+ |
0551, 0553, and 0555 IBM racks |
|
Table 11. 7109 PDU+ specifications| Characteristics |
Properties |
| PDU number |
7109 |
| Height |
43.9 mm (1.73 in.) |
| Width |
447 mm (17.6 in.) |
| Depth |
350 mm (13.78 in.) |
| Additional clearance |
25 mm (0.98 in.) for circuit breakers |
| 3 mm (0.12 in.) for outlets |
| Weight (not including power cord) |
6.3 kg (13.8 lb) |
| Weight of power cord (approximate) |
5.4 kg (11.8 lb) |
| Operating temperature at 0 - 914 m (0 - 3000
ft) (room ambient) |
10°C - 32°C (50°F - 90°F) |
| Operating temperature at 914 - 2133 m (3000
- 7000 ft) (room ambient) |
10°C - 35°C (50°F - 95°F) |
| Operating humidity |
8% - 80% (noncondensing) |
| Localized air temperature in PDU |
60°C (140°F) maximum |
| Rated frequency (all feature codes) |
50 - 60 Hz |
| Circuit breakers |
Six double-pole branch rated circuit breakers
rated at 20 A |
| Power outlet |
12 IEC 320-C13 outlets rated at 10 A (VDE) or
15 A (UL/CSA) |