Models 8233-E8B and 8236-E8C server specifications
Server specifications provide detailed information for the IBM® Power 750 Express (8233-E8B) and the IBM Power 755 (8236-E8C) servers, including dimensions, electrical data, power, temperature, environment requirements, and service clearances.

- 8233-E8B / 1 x EPA2
- 8233-E8B / 2 x EPA2
- 8233-E8B / 3 x EPA2
- 8233-E8B / 4 x EPA2
- 8233-E8B / 1 x EPA3
- 8233-E8B / 2 x EPA3
- 8233-E8B / 3 x EPA3
- 8233-E8B / 4 x EPA3
- 8233-E8B and 8236-E8C/ 1 x EPA4 and EPA1
- 8233-E8B and 8236-E8C/ 2 x EPA4 and EPA1
- 8233-E8B and 8236-E8C/ 3 x EPA4 and EPA1
- 8233-E8B and 8236-E8C/ 4 x EPA4 and EPA1
- 8233-E8B / 1 x 8335
- 8233-E8B / 2 x 8335
- 8233-E8B / 3 x 8335
- 8233-E8B / 4 x 8335
- 8233-E8B / 1 x 8334
- 8233-E8B / 2 x 8332
- 8233-E8B / 3 x 8332
- 8233-E8B / 4 x 8336
- 8236-E8C
Dimensions
| Width | Depth | Height | EIA units | Weight |
|---|---|---|---|---|
| 440 mm (17.3 in.) | 730 mm (28.7 in.) | 173 mm (6.81 in.) | 4 | 48.7 kg (107.4 lb) |
| Width | Depth | Height | Weight1 |
|---|---|---|---|
| 610 mm ( 24 in.) | 711 mm (28 in.) | 1016 mm (40 in.) | 68 - 113 kg (150 - 250 lb) |
| 1This is an estimated value. | |||
| Width | Depth | Height | Weight1 |
|---|---|---|---|
| 610 mm (24 in.) | 597 mm (23.5 in.) | 1016 mm (40 in.) | 68 - 113 kg (150 - 250 lb) |
| 1This is an estimated value. | |||
Environment requirements
| Environment | Temperature |
|---|---|
| Recommended operating temperature | 18 - 27°C (64 - 80°F) |
| Allowable operating temperature | 5 - 35°C (41- 95°F) |
| Nonoperating temperature | 5 - 45°C (41 - 113°F) |
| Recommended relative humidity range | 5.5°C (42°F) dew point to 60% RH and 15°C (59°F) dew point |
| Allowable relative humidity range | 20-80% |
| Nonoperating relative humidity range | 8 - 80% |
| Shipping temperature2 | -40 - 60°C (-40 - 140°F) |
| Shipping humidity range | 5 - 100% |
| Operating dew point | 28°C (84°F) |
| Altitude range | 0 - 3050 m1 |
1 Derate maximum dry-bulb temperature 1°C/300 m above 900 m. 2 The maximum wet bulb temperature is 29°C (84°F). If one or more feature codes that are listed in Table 5 are installed, then the maximum wet bulb temperature is 28°C (82°F). |
|
| Feature codes (FCs) | Feature code names |
|---|---|
1738 / EQ38 |
856 GB (IBM i) 10K RPM SAS HDD (Gen2-S) |
1752 / EQ52 |
900 GB (AIX/Linux) 10K RPM SAS HDD (Gen2-S) |
1917 / 1866 |
146 GB (AIX/Linux) 15K RPM SAS HDD (Gen2-S) |
1925 / 1869 |
300 GB (AIX/Linux) 10K RPM SAS HDD (Gen2-S) |
1947 / 1868 |
139 GB (IBM i) 15K RPM SAS HDD (Gen2-S) |
1948 / 1927 |
283 GB (IBM i) 15K RPM SAS HDD (Gen2-S) |
1953 / 1929 |
300 GB (AIX/Linux) 15K RPM SAS HDD (Gen2-S) |
1956 / 1844 |
283 GB (IBM i) 10K RPM SAS HDD (Gen2-S) |
1962 / 1817 |
571 GB (IBM i) 10K RPM SAS HDD (Gen2-S) |
1964 / 1818 |
600 GB (AIX/Linux) 10K RPM SAS HDD (Gen2-S) |
ESD2 / EQD2 |
1.14 TB (IBM i) 10K RPM SAS HDD (Gen2-S) |
ESD3 / EQD3 |
1.2 TB (AIX/Linux) 10K RPM SAS HDD (Gen2-S) |
Note:
|
|
Electrical
| Electrical characteristics | Properties |
|---|---|
| Maximum kVA | 2.0 kVA |
| Voltage | 200 - 240 V ac |
| Frequency | 47 - 63 Hz |
| Maximum thermal output | 6655 BTU/hr |
| Maximum power consumption | 1950 W |
| Power factor | 0.98 |
| Maximum inrush current | 70 Amps |
| Maximum leakage current | 0.77 mA |
| Phase | 1 |
| Maximum branch circuit breaker | 20 A |
Notes:
|
|
| Electrical characteristics | Properties |
|---|---|
| Circuit breaker rating | Minimum: 50 amps |
| Maximum: 50 amps | |
| Wire size | 8 AWG (IBM PN 44V4859 DC power cable from PDP output to server input) n/a: mm2 |
| Wiring-terminal screw torque | n/a: inch-pounds (IBM PN 44V4859 provided with connector, both ends) n/a: newton-meters |
Service clearances
| Clearances | Front | Back | Left or right | Top |
|---|---|---|---|---|
| Operating | 762 mm (30 in.) | 762 mm (30 in.) | ||
| Nonoperating | 762 mm (30 in.) | 762 mm (30 in.) | 762 mm (30 in.) | 762 mm (30 in.) |
Noise emissions
| Product description | Declared A-weighted sound power level, LWad (B) | Declared A-weighted sound pressure level, LpAm (dB) | ||
|---|---|---|---|---|
| Operating | Idle | Operating | Idle | |
| Two 3.3 GHz 6-core processors, 16 8 GB DIMMs, two power supplies, 8 SFF disk units, 1 DVD, and three PCI adapters | 6.4 | 6.2 | 47 | 45 |
| Two 3.3 GHz 6-core processors, 16 8 GB DIMMs,
two power supplies, 8 SFF disk units, 1 DVD, and three PCI adapters With Acoustical Doors |
5.8 | 5.6 | 40 | 39 |
| Four 3.3 GHz 6-core processors, 32 8 GB DIMMs, two power supplies, 8 SFF disk units, 1 DVD, and three PCI adapters | 7.1 | 7.1 | 53 | 53 |
| Four 3.3 GHz 6-core processors, 32 8 GB DIMMs,
two power supplies, 8 SFF disk units, 1 DVD, and three PCI adapters With Acoustical Doors |
6.5 | 6.5 | 48 | 48 |
Notes:
|
||||
Electromagnetic compatibility compliance
The electromagnetic compatibility compliance is: FCC Part 15, ICES-003
Safety compliance
The safety compliance is: IEC 60950-1; UL 60950; CSA 60950
Special Hardware Management Console considerations
When the server is managed by a Hardware Management Console (HMC), the console must be provided within the same room and within 8 m (26 ft) of the server. For additional considerations, see Planning for HMC installation and configuration.
Delivery and subsequent transportation of the equipment
You must prepare your environment, with assistance from an authorized service provider, to accept the new product based on the installation planning information provided. In anticipation of the equipment delivery, prepare the final installation site in advance so that professional movers or riggers can transport the equipment to the final installation site within the computer room. If, for some reason, this is not possible at the time of delivery, you must make arrangements to have professional movers or riggers return to finish the transportation at a later date. Only professional movers or riggers should transport the equipment. The authorized service provider can only perform minimal frame repositioning within the computer room, as needed, to perform required service actions. You are also responsible for using professional movers or riggers when you relocate or dispose of equipment.