POWER7 information

Models 8233-E8B and 8236-E8C server specifications

Server specifications provide detailed information for the IBM® Power 750 Express (8233-E8B) and the IBM Power 755 (8236-E8C) servers, including dimensions, electrical data, power, temperature, environment requirements, and service clearances.

Dimensions

Table 1. Dimensions. This table provides the dimensions for the 8233-E8B and 8236-E8C servers.
Width Depth Height EIA units Weight
440 mm (17.3 in.) 730 mm (28.7 in.) 173 mm (6.81 in.) 4 48.7 kg (107.4 lb)
Table 2. Shipping dimensions - Rack-mounted drawer
Width Depth Height Weight1
610 mm ( 24 in.) 711 mm (28 in.) 1016 mm (40 in.) 68 - 113 kg (150 - 250 lb)
1This is an estimated value.
Table 3. Shipping dimensions - Rack-mounted drawer (China)
Width Depth Height Weight1
610 mm (24 in.) 597 mm (23.5 in.) 1016 mm (40 in.) 68 - 113 kg (150 - 250 lb)
1This is an estimated value.

Environment requirements

Table 4. Environment requirements. This table provides the recommended temperatures, humidity, and altitude for the 8233-E8B and 8236-E8C servers.
Environment Temperature
Recommended operating temperature 18 - 27°C (64 - 80°F)
Allowable operating temperature 5 - 35°C (41- 95°F)
Nonoperating temperature 5 - 45°C (41 - 113°F)
Recommended relative humidity range 5.5°C (42°F) dew point to 60% RH and 15°C (59°F) dew point
Allowable relative humidity range 20-80%
Nonoperating relative humidity range 8 - 80%
Shipping temperature2 -40 - 60°C (-40 - 140°F)
Shipping humidity range 5 - 100%
Operating dew point 28°C (84°F)
Altitude range 0 - 3050 m1

1 Derate maximum dry-bulb temperature 1°C/300 m above 900 m.

2 The maximum wet bulb temperature is 29°C (84°F). If one or more feature codes that are listed in Table 5 are installed, then the maximum wet bulb temperature is 28°C (82°F).

Table 5. Supported feature codes that affect environmental requirements1
Feature codes (FCs) Feature code names

1738 / EQ38

856 GB (IBM i) 10K RPM SAS HDD (Gen2-S)

1752 / EQ52

900 GB (AIX/Linux) 10K RPM SAS HDD (Gen2-S)

1917 / 1866

146 GB (AIX/Linux) 15K RPM SAS HDD (Gen2-S)

1925 / 1869

300 GB (AIX/Linux) 10K RPM SAS HDD (Gen2-S)

1947 / 1868

139 GB (IBM i) 15K RPM SAS HDD (Gen2-S)

1948 / 1927

283 GB (IBM i) 15K RPM SAS HDD (Gen2-S)

1953 / 1929

300 GB (AIX/Linux) 15K RPM SAS HDD (Gen2-S)

1956 / 1844

283 GB (IBM i) 10K RPM SAS HDD (Gen2-S)

1962 / 1817

571 GB (IBM i) 10K RPM SAS HDD (Gen2-S)

1964 / 1818

600 GB (AIX/Linux) 10K RPM SAS HDD (Gen2-S)

ESD2 / EQD2

1.14 TB (IBM i) 10K RPM SAS HDD (Gen2-S)

ESD3 / EQD3

1.2 TB (AIX/Linux) 10K RPM SAS HDD (Gen2-S)

Note:
  1. Any feature code that is listed in this table and is installed in your system decreases the maximum wet bulb temperature that is allowed during shipping from 29°C (84°F) to 28°C (82°F).

Electrical

Table 6. Alternating current electrical. This table provides the electrical information for the 8233-E8B and 8236-E8C servers.
Electrical characteristics Properties
Maximum kVA 2.0 kVA
Voltage 200 - 240 V ac
Frequency 47 - 63 Hz
Maximum thermal output 6655 BTU/hr
Maximum power consumption 1950 W
Power factor 0.98
Maximum inrush current 70 Amps
Maximum leakage current 0.77 mA
Phase 1
Maximum branch circuit breaker 20 A
Notes:
  1. The power supplies automatically accept any voltage with the published, rated-voltage range. During standard operation, dual power supplies are operating, the power supplies draw approximately equal current from the utility (mains) and provide approximately equal current to the load.
  2. Power draw and heat load vary greatly by configuration. When planning for an electrical system, it is important to use maximum values. However, when planning for heat load, you can use the IBM Systems Energy Estimator to obtain a heat output estimate based on a specific configuration.
  3. Measured according to IEC 60950.
  4. To calculate the amperage, multiply the kVA by 1000 and divide that number by the operating voltage.
Table 7. Direct current electrical for the 8233-E8B. This table provides information on the Power Distribution Panel (PDP) and its connection to a -48 V dc 8233-E8B server.
Electrical characteristics Properties
Circuit breaker rating Minimum: 50 amps
Maximum: 50 amps
Wire size

8 AWG (IBM PN 44V4859 DC power cable from PDP output to server input)

n/a: mm2

Wiring-terminal screw torque

n/a: inch-pounds (IBM PN 44V4859 provided with connector, both ends)

n/a: newton-meters

Service clearances

Table 8. Service clearances
Clearances Front Back Left or right Top
Operating 762 mm (30 in.) 762 mm (30 in.)  
Nonoperating 762 mm (30 in.) 762 mm (30 in.) 762 mm (30 in.) 762 mm (30 in.)

Noise emissions

Table 9. Noise emissions
Product description Declared A-weighted sound power level, LWad (B) Declared A-weighted sound pressure level, LpAm (dB)
  Operating Idle Operating Idle
Two 3.3 GHz 6-core processors, 16 8 GB DIMMs, two power supplies, 8 SFF disk units, 1 DVD, and three PCI adapters 6.4 6.2 47 45
Two 3.3 GHz 6-core processors, 16 8 GB DIMMs, two power supplies, 8 SFF disk units, 1 DVD, and three PCI adapters

With Acoustical Doors

5.8 5.6 40 39
Four 3.3 GHz 6-core processors, 32 8 GB DIMMs, two power supplies, 8 SFF disk units, 1 DVD, and three PCI adapters 7.1 7.1 53 53
Four 3.3 GHz 6-core processors, 32 8 GB DIMMs, two power supplies, 8 SFF disk units, 1 DVD, and three PCI adapters

With Acoustical Doors

6.5 6.5 48 48
Notes:
  1. LWAD is the statistical upper-limit A-weighted sound power level (rounded to the nearest 0.1 B).
  2. LPAM is the mean A-weighted emission sound pressure level measured at the 1-meter bystander positions (rounded to the nearest dB).
  3. 10 dB (decibel) equals 1 B (bel).
  4. All measurements made in conformance with ISO 7779 and declared in conformance with ISO 9296.

Electromagnetic compatibility compliance

The electromagnetic compatibility compliance is: FCC Part 15, ICES-003

Safety compliance

The safety compliance is: IEC 60950-1; UL 60950; CSA 60950

Special Hardware Management Console considerations

When the server is managed by a Hardware Management Console (HMC), the console must be provided within the same room and within 8 m (26 ft) of the server. For additional considerations, see Planning for HMC installation and configuration.

Note: As an alternative to the local HMC requirement, it is acceptable for you to provide a supported device, such as a PC, with connectivity and authority to operate through a remotely attached HMC. This local device must be in the same room and within 8 m (26 ft.) of your server, and provide functional capability equivalent to the HMC that it replaces and that is needed by the service representative to service the system.

Delivery and subsequent transportation of the equipment

DANGER
Heavy equipment—personal injury or equipment damage might result if mishandled. (D006)

You must prepare your environment, with assistance from an authorized service provider, to accept the new product based on the installation planning information provided. In anticipation of the equipment delivery, prepare the final installation site in advance so that professional movers or riggers can transport the equipment to the final installation site within the computer room. If, for some reason, this is not possible at the time of delivery, you must make arrangements to have professional movers or riggers return to finish the transportation at a later date. Only professional movers or riggers should transport the equipment. The authorized service provider can only perform minimal frame repositioning within the computer room, as needed, to perform required service actions. You are also responsible for using professional movers or riggers when you relocate or dispose of equipment.



Send feedback Rate this page

Last updated: Thu, March 15, 2018