Model 7014-T00 rack
Hardware specifications provide detailed information for your rack, including dimensions, electrical, power, temperature, environment, and service clearances.
| Dimensions | Properties |
|---|---|
| Height | 1804 mm (71.0 in.) |
| Capacity | 36 usable EIA units |
| Height with PDP - DC only | 1926 mm (75.8 in.) |
| Width without side panels | 623 mm (24.5 in.) |
| Width with side panels | 644 mm (25.4 in) |
| Depth with rear door only | 1042 mm (41.0 in.) |
| Depth with rear door and front door | 1098 mm (43.3 in.) |
| Depth with sculptured style front door | 1147 mm (45.2 in.) |
| Base rack (empty) | Full rack |
|---|---|
| 244 kg (535 lb) | 816 kg (1795 lb) See 7014-T00, 7014-T42 and 0553 rack weight distribution and floor loading |
| Electrical characteristics | Properties |
|---|---|
| DC rack voltage (nominal) | -48 V dc |
| Power source loading maximum in kVa2 | See Power distribution unit and power cord options for 7014, 0551, 0553, and 0555 rack for details |
| Voltage range (V dc) | -40 - -60 |
| AC rack | 683 Btu/hr |
| Power source loading maximum in kVa (per PDB)3 | 135 W |
| Voltage range (V ac) | 200 - 240 |
| Frequency (Hz) | 50 or 60 |
1The total rack power should be derived from the sum of the power used by the drawers in the rack. 2The power distribution panel (PDP) on the DC-powered rack can hold up to eighteen (nine per power source) 48-volt, 20 - 50 amperes circuit breakers (configuration dependent). Each power source supports up to 8.4 kVa. 3Each ac power distribution bus (PDB) can supply 4.8 kVa. A rack can have up to four PDBs as required by the drawers mounted in the rack. |
|
| Front | Back | Sides |
|---|---|---|
| 915 mm (36 in.) | 915 mm (36 in.) | 915 mm (36 in.) |
See your server or hardware specifications for specific temperature and humidity requirements.