subscribe iconSubscribe to this information

Model 9110-510, OpenPower 710 (9123-710), and 9110-51A server specifications

Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.

Use the following specifications to plan for your server.

Table 1. Dimensions - Rack-mounted drawer
Measurements Width Depth Height EIA units1 Weight
Metric 437 mm 691 mm 88.9 mm 2 23 kg
English 17.20 in. 27.2 in. 3.5 in. 51 lb
Table 2. Shipping dimensions - Rack-mounted drawer
Measurements Width Depth Height Weight
Metric 635 mm 864 mm 457 mm 53 kg
English 25 in. 34 in. 18 in. 117 lb
Table 3. Shipping dimensions - Rack-mounted drawer (China)
Measurements Width Depth Height Weight
Metric 635 mm 864 mm 457 mm 53 kg
English 25 in. 34 in. 18 in. 117 lb

Feature code for drawer mounted in rack

Power distribution unit and power cord options for 7014, 0551, or 0553, 0551, and 7014-T00 racks

7998

7999

 
Table 4. Electrical
Electrical characteristics Properties
kVA (maximum)

0.500 ( 9110-510 OpenPower™ 710)

0.658 (9110-51A with 4-core, 1.5 GHz processor configuration)

Rated voltage and frequency 100 - 127 or 200-240V ac at 50/60 plus or minus 0.5 Hz
Thermal output (maximum)

1622 Btu/hr ( 9110-510 OpenPower 710)

2133 Btu/hr (9110-51A with 4-core, 1.5 GHz processor configuration)

Maximum power consumption

475 W ( 9110-510 OpenPower 710)

625 W (9110-51A with 4-core, 1.5 GHz processor configuration)

Power factor 0.95
Inrush current (maximum) 75 A
Leakage current (maximum) 1.2 mA
Phase 1
Dual power feature code 7989 (quantity 2)
Branch circuit breaker 20 A (maximum)
Table 5. Environment requirements
Environment Temperature
Recommended operating temperature 1 5 - 35 °C (41 - 95 °F)
Nonoperating temperature 5 - 45 °C (41 - 113 °F)
Shipping temperature -40 - 60 °C (-40 - 140 °F)
Operating Nonoperating
Maximum dew point 28 °C (82 - °F) 29 °C (84.2 - °F)
Noncondensing humidity 8 - 80% 8 - 80%
Maximum altitude 3048 m (10 000 ft) 3048 m (10 000 ft)
1Class 3 product as defined in ASHRAE Thermal Guidelines for Data Processing Environments. The allowable operating range is 5 - 35 °C (41 - 95 °F). See the Temperature and humidity design criteria topic for more information.
Table 6. Noise emissions
Product description Declared A-weighted sound power level Declared A-weighted sound power level
LWAd (Category 2D, General business) – rack drawer 6.2 bels1 6.2 bels1
LpAm (1-meter bystander) 44 dB1 44 dB1

1 Preliminary data.

For a description of noise emission values, see Acoustics.

Table 7. Service clearances
Clearances Front Back Left or right Top
Operating 762 mm (30 in.) 762 mm (30 in.) Not applicable Not applicable
Nonoperating 762 mm (30 in.) 762 mm (30 in.) 762 mm (30 in.) 762 mm (30 in.)

Electromagnetic compatibility compliance: This server meets the following electromagnetic compatibility specifications: FCC (CFR 47, Part 15); VCCI; CISPR-22; 89/336/EEC; BSMI (A2/NZS 3548:1995); C-Tick; ICES/NMB-003; Korean EMI/EMC (MIC Notice 2000–94, Notice 2000–72); People's Republic of China Commodity Inspection Law

Safety compliance: This server is designed and certified to meet the following safety standards: UL 60950; CAN/CSA C22.2 No. 60950–00; EN 60950; IEC 60950 including all National Differences

See 0551, 0553, 7014, and 0555 rack configurations for typical configurations when the 0551, 0553, 7014, or 0555 rack is populated with various server models.


Send feedback | Rate this page