Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.
Use the following specifications to plan for your server.
| Measurements | Width | Depth | Height | EIA units1 | Weight |
|---|---|---|---|---|---|
| Metric | 437 mm | 691 mm | 88.9 mm | 2 | 23 kg |
| English | 17.20 in. | 27.2 in. | 3.5 in. | 51 lb |
| Measurements | Width | Depth | Height | Weight |
|---|---|---|---|---|
| Metric | 635 mm | 864 mm | 457 mm | 53 kg |
| English | 25 in. | 34 in. | 18 in. | 117 lb |
| Measurements | Width | Depth | Height | Weight |
|---|---|---|---|---|
| Metric | 635 mm | 864 mm | 457 mm | 53 kg |
| English | 25 in. | 34 in. | 18 in. | 117 lb |
| Feature code for drawer mounted in rack Power distribution unit and power cord options for 7014, 0551, or 0553, 0551, and 7014-T00 racks |
7998 7999 |
|||
| Electrical characteristics | Properties |
|---|---|
| kVA (maximum) | 0.500 ( 9110-510 OpenPower™ 710) 0.658 (9110-51A with 4-core, 1.5 GHz processor configuration) |
| Rated voltage and frequency | 100 - 127 or 200-240V ac at 50/60 plus or minus 0.5 Hz |
| Thermal output (maximum) | 1622 Btu/hr ( 9110-510 OpenPower 710) 2133 Btu/hr (9110-51A with 4-core, 1.5 GHz processor configuration) |
| Maximum power consumption | 475 W ( 9110-510 OpenPower 710) 625 W (9110-51A with 4-core, 1.5 GHz processor configuration) |
| Power factor | 0.95 |
| Inrush current (maximum) | 75 A |
| Leakage current (maximum) | 1.2 mA |
| Phase | 1 |
| Dual power feature code | 7989 (quantity 2) |
| Branch circuit breaker | 20 A (maximum) |
| Environment | Temperature | |
|---|---|---|
| Recommended operating temperature 1 | 5 - 35 °C (41 - 95 °F) | |
| Nonoperating temperature | 5 - 45 °C (41 - 113 °F) | |
| Shipping temperature | -40 - 60 °C (-40 - 140 °F) | |
| Operating | Nonoperating | |
| Maximum dew point | 28 °C (82 - °F) | 29 °C (84.2 - °F) |
| Noncondensing humidity | 8 - 80% | 8 - 80% |
| Maximum altitude | 3048 m (10 000 ft) | 3048 m (10 000 ft) |
| 1Class 3 product as defined in ASHRAE Thermal Guidelines for Data Processing Environments. The allowable operating range is 5 - 35 °C (41 - 95 °F). See the Temperature and humidity design criteria topic for more information. | ||
| Product description | Declared A-weighted sound power level | Declared A-weighted sound power level |
|---|---|---|
| LWAd (Category 2D, General business) – rack drawer | 6.2 bels1 | 6.2 bels1 |
| LpAm (1-meter bystander) | 44 dB1 | 44 dB1 |
1 Preliminary data. For a description of noise emission values, see Acoustics. |
||
| Clearances | Front | Back | Left or right | Top |
|---|---|---|---|---|
| Operating | 762 mm (30 in.) | 762 mm (30 in.) | Not applicable | Not applicable |
| Nonoperating | 762 mm (30 in.) | 762 mm (30 in.) | 762 mm (30 in.) | 762 mm (30 in.) |
Electromagnetic compatibility compliance: This server meets the following electromagnetic compatibility specifications: FCC (CFR 47, Part 15); VCCI; CISPR-22; 89/336/EEC; BSMI (A2/NZS 3548:1995); C-Tick; ICES/NMB-003; Korean EMI/EMC (MIC Notice 2000–94, Notice 2000–72); People's Republic of China Commodity Inspection Law
Safety compliance: This server is designed and certified to meet the following safety standards: UL 60950; CAN/CSA C22.2 No. 60950–00; EN 60950; IEC 60950 including all National Differences
See 0551, 0553, 7014, and 0555 rack configurations for typical configurations when the 0551, 0553, 7014, or 0555 rack is populated with various server models.