Server specifications provide detailed information for
your server, including dimensions, electrical, power, temperature,
environment, and service clearances.
Use the following specifications to plan for your server.
Note: Redundant
power and power cords are standard on model 9406-825. The server uses
dual alternating current power cords. For maximum availability, each
of the power cords should be fed from independent power grids.
The
5094 and 5095 expansion units are available with model 9406-825.
Table 1. Dimensions| Dimensions |
Width |
Depth |
Height |
Maximum configuration weight |
Height in 0551 rack2, 4 |
| Metric |
445 mm |
830 mm |
610 mm |
110 kg |
16 EIA |
| English |
17.5 in. |
32.7 in. |
24 in. |
242 lb |
16 U |
Table 2. Electrical| Electrical characteristics |
Property |
| kVA |
1.540 |
| Thermal output (Btu/hr) |
4993 |
| Power requirements (watts) |
1463 |
| Rated voltage and frequency 3-core,
4-core, 5-core, and 6-core5 |
200 - 240 V ac at 50-60 plus
or minus 0.5 Hz |
| Power factor |
0.95 |
| Inrush current |
125 A |
| Leakage current (maximum) |
3.5 mA |
| Phase |
1 |
Table 3. Temperature requirements| Operating |
Nonoperating |
| 10 - 38°C (50 - 100.4°F) |
1 - 60°C (33.8 - 140°F) |
Table 4. Environment requirements| Environment |
Operating |
Nonoperating |
| Noncondensing humidity |
8 - 80% |
8 - 80% |
| Wet bulb temperature |
23°C (73.4°F) |
27°C (80.6°F) |
| Maximum altitude |
3048 m (10 000 ft) |
|
Table 5. Noise emissions1| Property |
Operating |
Idle |
| LWAd (Category 2D, General business) |
6.8 bels |
6.8 bels |
| LpAm (1-meter bystander) |
50 dB |
49 dB |
Table 6. Service clearances| Front |
Back |
Sides3 |
Top3 |
| 762 mm |
762 mm |
762 mm |
762 mm |
| 30 in. |
30 in. |
30 in. |
30 in. |
Table 7. NotesNotes: - For a description of noise emission values, see Acoustics.
- Feature codes 0134 and 0138 are both field install in rack.
- Side and top clearances are optional when operating.
- See 0551 rack configurations for typical configurations
when the 0551 rack is populated with various server models.
- The power supplies automatically accept any voltage with the published
rated voltage range. If dual power supplies are installed and operating,
the power supplies draw approximately equal current from the utility
(mains) and provide approximately equal current to the load.
|
Delivery
and subsequent transportation of the equipment
DANGER
Heavy equipment—personal injury or equipment
damage might result if mishandled. (D006)
You must
prepare your environment to accept the new product based on the installation
planning information provided, with assistance from an IBM® Installation Planning Representative
(IPR) or IBM authorized
service provider. In anticipation of the equipment delivery, prepare
the final installation site in advance so that professional movers
or riggers can transport the equipment to the final installation site
within the computer room. If for some reason, this is not possible
at the time of delivery, you must make arrangements to have professional
movers or riggers return to finish the transportation at a later date.
Only professional movers or riggers should transport the equipment.
The IBM authorized
service provider can only perform minimal frame repositioning within
the computer room, as needed, to perform required service actions.
You are also responsible for using professional movers or riggers
when you relocate or dispose of equipment.