Server specifications provide detailed information for
your server, including dimensions, electrical, power, temperature,
environment, and service clearances.
Use the following specifications to plan for your server.
The
5074 expansion unit, 5078 expansion unit, 8079 optional 1.8 m model
9406-840 I/O rack or 5079 1.8 m expansion unit are available with
model 9406-840 or model SB3 servers.
Table 1. Dimensions| Measurements |
Maximum configuration weight |
Width |
Depth |
Height |
| Metric |
397 kg |
565 mm |
1320 mm |
1577 mm |
| English |
875 lb |
22.3 in. |
52.0 in. |
62.0 in. |
Table 2. Electrical| Electrical |
Properties |
| kVA (maximum) |
2.526 |
| Rated voltage and frequency3 |
200-240 V ac at 50-60 plus or
minus 0.5 Hz |
| Thermal output (maximum) |
8191 Btu/hr |
| Power requirements (maximum) |
2400 W |
| Power factor |
0.95 |
| Inrush current |
100 A |
| Leakage current (maximum) |
3.5 mA |
| Phase |
1 |
Table 3. Temperature requirements| Operating |
Nonoperating |
| 10 - 38°C (50 - 100.4°F) |
1 - 60°C (33.8 - 140°F) |
Table 4. Environment requirements| |
Operating |
Nonoperating |
| Noncondensing humidity
|
8 - 80% |
8 - 80% |
| Wet bulb temperature |
22.8°C (73°F) |
27°C (80.6°F) |
| Maximum
altitude |
3048 m (10000 ft) |
|
Table 5. Noise emissions1 | |
Operating |
Idle |
| LWAd (Category 2D,
General business) |
7.0 bels |
6.9 bels |
| LpAm (1-meter bystander) |
51 dB |
51 dB |
Table 6. Service clearances| Front |
Back |
Sides2 |
Top2 |
| 762 mm |
762 mm |
762 mm |
762 mm |
| 30 in. |
30 in. |
30 in. |
30 in. |
Table 7. NotesNotes:
- For a description of noise emission values, see Acoustics.
- Side and top clearances are optional when operating
- The power supplies automatically accept any voltage with the published
rated voltage range. If dual power supplies are installed and operating,
the power supplies draw approximately equal current from the utility
(mains) and provide approximately equal current to the load.
|