7314-G30 and 5796 expansion unit

Hardware specifications provide detailed information for your expansion unit, including dimensions, electrical, power, temperature, environment, and service clearances.

Table 1. Dimensions I/O drawer only
Dimensions Height Width Depth
Metric 172 mm 224 mm 800 mm
English 6.8 in. 8.8 in. 31.5 in.
Table 2. Dimensions - with required I/O drawer mounting enclosure
Dimensions Height Width Depth
Metric 176 mm 473 mm 800 mm
English 6.9 in. 18.6 in. 31.5 in.
Table 3. Maximum configuration weight
One I/O drawer Two I/O drawers plus the mounting enclosure
20 kg (44 lb) 45.9 kg (101 lb)
Table 4. Electrical
Electrical characteristics Properties
kVA 0.275
Rated voltage and frequency 200 - 240 V ac at 50 - 60 Hz, V dc not supported
Thermal output 853 Btu/hr
Power requirements (maximum) 250 W
Power factor 0.91
Inrush current per 7314-G302 60 A
Table 5. Temperature requirements3
Operating Nonoperating Storage
10 - 38°C (50 - 100°F) 1 - 60°C (33.8 - 140°F) 1 - 60°C (33.8 - 140°F)
Table 6. Environment requirements
Environment Operating Nonoperating Storage
Noncondensing humidity 8 - 80% 8 - 80% 5 - 80%
Wet bulb temperature4 23°C (73.4°F) 27°C (80.6°F) 29°C (84.2°F)
Table 7. Maximum altitude
3048 m (10 000 ft)
Table 8. Noise emissions1
Properties Operating Idle
LWAd 6.2 bels 6.1 bels
<LpA>m 44 dB 43 dB
Table 9. Service clearances
Dimensions Front Back Sides
Metric 915 mm 915 mm 915 mm
English 36 in. 36 in. 36 in.
Table 10. Notes
Notes:
  1. For a description of noise emission values, see Acoustics.
  2. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
  3. The upper limit of the dry bulb temperature must be derated 1°C per 137 m (450 ft) above 915 m (3000 ft).
  4. The upper limit of the wet bulb temperature must be derated 1°C per 274 m (900 ft) above 305 m (1000 ft).