You might need to connect a dc power source to the rack. Use the
procedure in this section to perform this task.
Note: The customer is responsible for providing and connecting
the -48 V dc power source and -48 V dc power return cables from the customer's
source -48 V dc to the bus bars in the power distribution panel. The customer
is also responsible for connecting the ground cable to the rack frame. This
procedure provides information about accessing the power distribution panel.
- Remove the six mounting screws from the top cover of the dc power
distribution panel and remove the top cover.
- If installed, remove the four screws from the cable channel cover.
- Remove the cable channel cover.
| 1 |
Cable channel cover retaining screw |
5 |
Shield |
| 2 |
Cable channel cover |
6 |
Power distribution panel |
| 3 |
Power distribution panel top cover retaining screws |
7 |
Front of rack |
| 4 |
Power distribution panel top cover |
|
|
Figure 1. Removing the cable channel cover.
- Remove the -48 V dc bus bar shield from the power distribution
panel.
Attention: The bus bar shield must be correctly
reinstalled over the -48 V dc return bus bars to protect against injury while
servicing the power distribution panel.
- Ensure that the following steps are performed when connecting the
dc power source.
- At -48 V dc power source, turn off any -48 V dc power sources that will
be connected to the power distribution panel.
- After the -48 V dc power sources are turned off, be sure there is a tag
or label over the power source switches or fuses (lock-out/tag-out) to indicate
that the power source is turned off intentionally.
Note: Ensure that any
oxidation on the copper bus bars is removed.
- If this is a raised-floor installation and you are working at the back
of the rack, route the power cables up the rack's right side.
- Ensure that the external -48 V dc power cable is connected correctly to
the -48 V dc bus bar.
- Ensure that the external -48 V dc return cable is routed correctly and
installed on the return bus bar.
| 1 |
-48 V dc power cable and return power cable |
| 2 |
Power distribution panel |
| 3 |
Front of rack |
| 4 |
-48 V dc power cable and return power cable |
Figure 2. Routing the power cables.
| 1 |
Front of power distribution panel |
6 |
(B) Return (-) power cable |
| 2 |
(A) -48 V dc (-) bus bar |
7 |
(B) -48 V dc (-) power cable |
| 3 |
(A) -48 V dc (-) power cable |
8 |
(B) Return (-) bus bar |
| 4 |
(A) Return (-) bus bar |
9 |
(B) -48 V dc (-) bus bar |
| 5 |
(A) Return (-) power cable |
|
|
Figure 3. Return bus bar.
- If you want to install a power status alarm, connect the alarm cable to
the terminal board on the back cover of the dc power distribution panel.
Note: Ensure
that the oxidation on the copper bus bars is removed.
- Ensure that the power-source ground cable is routed correctly and connects
the power-source ground cable to the copper bar at the lower-back or upper-back
center of the rack.
- If the rack is on a raised floor, attach the -48 V dc power source cables
to the back of the rack with cable-restraint straps.
| 1 |
Back view of rack (dc) |
| 2 |
Power cable, power return cable, and ground |
| 3 |
Ground cable (Install at either top or bottom of the
rack) |
Figure 4. Cable locations.
- Reinstall the -48 V dc bus bar shield.
- Reinstall the top cover on the dc power distribution panel.
- Reinstall the cable channel cover.
| 1 |
Cable channel cover |
| 2 |
Terminal block (both sides) |
| 3 |
Power distribution panel |
| 4 |
Front of rack |
Figure 5. Reinstalling the cable channel cover.