Use the Plug and receptacle type by voltage and amperage table to determine the plugs and receptacles available for your system.
| Voltage and amperage | Plug and receptacle type | ||
|---|---|---|---|
| 100 -240 V, 10 (HV), 12 (LV) | Type 26 | ||
| 250 V, 16 A/phase | Type 46 3P+N+G | ||
| 250 V, 30 A | Type 12 | Type KP | Type PDL |
| 250 V, 32 A | Type 40 | Type 46 P+N+G [32A] | |
To determine the plug and receptacle type your model will need, follow these steps:
The Plug and receptacle type listed in the same row as your voltage and amperage supports your model.
If more than one plug appears in your row:
The plug and receptacle type that lists your Country or Region is the type for which you need to plan.
Note: If your Country or Region is not listed or, for some reason, you still cannot determine your plug and receptacle type, contact your seller.