Model 9406-825 server specifications

Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.

Use the following specifications to plan for your server.

Note: Redundant power and power cords are standard on the model 9406-825. The server uses dual alternating current power cords. For maximum availability, each of the power cords should be fed from independent power grids.

Table 1. Server specifications

Pictured is the model 9406-825 server.

The 5094 and 5095 expansion units are available with model 9406-825.

Dimensions are shown for model 9406-825 only.

model 9406-825

Dimensions 9406-825 Width 9406-825 Depth 9406-825 Height Height in 0551 rack2, 4
Metric 445 mm 830 mm 610 mm 16 EIA
English 17.5 in. 32.7 in. 24 in. 16 U
 
Maximum configuration weight 110 kg (242 lb.)
Electrical
kVA 1.540
Thermal output (Btu/hr) 4993
Power requirements (watts) 1463
Rated voltage and frequency 3-way, 4-way, 5-way, and 6-way5   200-240 V ac at 50-60 plus or minus 0.5 Hz
Power factor 0.95
Inrush current 125 A
Leakage current (maximum) 3.5 mA
Phase 1
Compatible plug types 5, 6, 10, 18, 19, 22, 23, 24, 25, 32, 34
Power cord length 2.7 m (9 ft.), 1.8 m (6 ft.) (U.S. and Canada only), 4.3 m (14 ft.)
Temperature requirements
Operating 10 degrees to 38 degrees C (50 degrees to 100.4 degrees F)
Nonoperating 1 degrees to 60 degrees C (33.8 degrees to 140 degrees F)
Environment requirements Operating Nonoperating
Noncondensing humidity 8 to 80% 8 to 80%
Wet bulb temperature 23 degrees C (73.4 degrees F) 27 degrees C (80.6 degrees F)
Maximum altitude 3048 m (10000 ft.)
Noise emissions1 Operating Idle
LWAd (Category 2D, General business) 6.8 bels 6.8 bels
LpAm (1-meter bystander) 50 dB 49 dB
Service clearances
Front Back Sides3 Top3
762 mm 762 mm 762 mm 762 mm
30 in. 30 in. 30 in. 30 in.

Notes:

  1. For a description of noise emission values, see the Acoustics chapter of the Site Preparation and Physical Planning Guide, SA76-0103.
  2. Feature codes 0134 and 0138 are both field install in rack.
  3. Side and top clearances are optional when operating.
  4. See 0551 rack configurations for typical configurations when the 0551 rack is populated with various server models.
  5. The power supplies automatically accept any voltage with the published rated voltage range. If dual power supplies are installed and operating, the power supplies draw approximately equal current from the utility (mains) and provide approximately equal current to the load.

Delivery and subsequent transportation of the equipment

DANGER
Heavy equipment—personal injury or equipment damage might result if mishandled. (D006)

You must prepare your environment to accept the new product based on the installation planning information provided, with assistance from an IBM® Installation Planning Representative (IPR) or IBM authorized service provider. In anticipation of the equipment delivery, prepare the final installation site in advance so that professional movers or riggers can transport the equipment to the final installation site within the computer room. If for some reason, this is not possible at the time of delivery, you must make arrangements to have professional movers or riggers return to finish the transportation at a later date. Only professional movers or riggers should transport the equipment. The IBM authorized service provider can only perform minimal frame repositioning within the computer room, as needed, to perform required service actions. You are also responsible for using professional movers or riggers when you relocate or dispose of equipment.