EMX0 PCIe Gen3 I/O expansion drawer (feature code EMX0)

Hardware specifications provide detailed information for your expansion unit, including dimensions, electrical, power, temperature, environment, and service clearances.

Table 1. Dimensions for rack-mounted expansion unit
Width Depth Height Weight (maximum)
482 mm (19 in.) 802 mm (31.6 in.) 173 mm (6.8 in.), 4 EIA units 54.4 kg (120 lb)
Table 2. Electrical1,2,3
Electrical characteristics Properties
AC rated voltage and frequency 100 - 127 V ac or 200 - 240 V ac at 50 or 60 Hz plus or minus 3 Hz (FC EMXA)
DC rated voltage 192 - 400 V dc (FC EMXB)
Thermal output (maximum) 1740 BTU/hr
Maximum power consumption 510 W
Maximum kVA 0.520
Phase Single
Notes:
  1. The power supplies for AC or DC voltage do not change. Only the power chunnel is different. The power chunnel uses internal cables to carry power from the rear of the system node to the power supplies that are in the front of the system node.
  2. All measurements made in conformance with ISO 7779 and declared in conformance with ISO 9296.
  3. AC and HVDC power supplies cannot be mixed in the same server or I/O drawer. IBM® recommends that AC products and HVDC products with HVDC PDUs are installed in separate racks. However, AC and HVDC products can be supported in the same rack if all grounding (earthing) is done in accordance with the applicable electrical code or codes. IBM provides documentation for different AC and HVDC products about the disconnecting means for service. If a different disconnecting means is to be used for service of the equipment in a rack with AC-powered and DC-powered products, the disconnecting means must be made clear to service.
Table 3. Environment requirements
Environment Recommended operating Allowable operating Nonoperating
ASHRAE class   A3  
Airflow direction   Front-to-back  
Temperature1 18°C - 27°C (64°F - 80°F) 5°C - 40°C (41°F - 104°F) 1°C - 60°C (34°F - 140°F)
Humidity range 5.5°C (42°F) dew point (DP) to 60% relative humidity (RH) and 15°C (59°F) dew point -12.0°C (10.4°F) DP and 8% - 80% RH 5% - 80% RH
Maximum dew point   24°C (75°F) 27°C (80°F) 
Maximum operating altitude   3050 m (10000 ft)  
Shipping temperature     -40°C to 60°C (-40°F to 140°F)
Shipping relative humidity     5% - 100%
  1. Derate maximum allowable dry-bulb temperature 1°C per 175 m above 950 m.
Table 4. Service clearances for rack-mounted expansion unit
Front Back Sides
914 mm (36 in.) 914 mm (36 in.) 914 mm (36 in.)
Side and top clearances are optional during operation.