Model 7953-94X and 7965-94Y rack
Hardware specifications provide detailed information for your rack, including dimensions, electrical, power, temperature, environment, and service clearances.
| Width | Depth | Height | Weight (Empty) | Weight (Maximum configuration) | EIA unit capacity | |
|---|---|---|---|---|---|---|
| Rack only | 600 mm (23.6 in.) | 1095 mm (43.1 in.) | 2002 mm (78.8 in.) | 130 kg (287 lb) | 1140 kg (2512 lb) | 42 EIA units |
| Rack with standard doors | 600 mm (23.6 in.) | 1145.5 mm (45. in.) | 2002 mm (78.8 in.) | 138 kg (304 lb) | N/A | N/A |
| Rack with triplex doors | 600 mm (23.6 in.) | 1206.2 - 1228.8 mm (47.5 - 48.4 in.) | 2002 mm (78.8 in.) | 147 kg (324 lb) | N/A | N/A |
| Rack with rear door heat exchanger indicator | 600 mm (23.6 in.) | 1224 mm (48.2 in.) | 2002 mm (78.8 in.) | 169 kg (373 lb) | N/A | N/A |
|
Note: When the rack is delivered or is moved, outriggers are needed for stability. For more
information about outriggers, see Side stabilizing
outriggers.
|
||||||
| Door model | Width | Height | Depth | Weight |
|---|---|---|---|---|
|
Standard front door (FC EC01) and standard back door (FC EC02) |
597 mm (23.5 in.) |
1925 mm (75.8 in.) | 22.5 mm (0.9 in.) | 7.7 kg (17 lb) |
| Triplex door (FC EU21)3 |
597.1 mm (23.5 in.) |
1923.6 mm (75.7 in.) | 105.7 mm (4.2 in.)1 | 16.8 kg (37 lb) |
| 128.3 mm (5.2 in.)2 | ||||
|
1 Measured from the front flat surface of the door. 2 Measured from the IBM® logo on the front of the door. 3 Multiple racks that are placed side-by-side must have a 6 mm (0.24 in.) minimum clearance between racks to allow the triplex front door to hinge properly. Feature code EC04 (Rack suite attachment kit) can be used to maintain the 6 mm (0.24 in.) minimum clearance between racks. |
||||
| Depth | Height | Weight |
|---|---|---|
| 885 mm (34.9 in.) | 1870 mm (73.6 in.) | 17.7 kg (39 lb) |
| 1 Side covers do not increase the overall width of the rack. | ||
| Operating | Nonoperating |
|---|---|
| 10°C - 38°C (50°F - 100.4°F)1 | -40°C to 60°C (-40°F to 140°F) |
| 1 The maximum 38°C (100.4°F) temperature must be derated 1°C (1.8 °F) per 137 m (450 ft) above 1295 m (4250 ft). | |
| Environment | Operating | Nonoperating | Maximum altitude |
|---|---|---|---|
| Noncondensing humidity | 20% - 80% (allowable) 40% - 55% (recommended) |
8% - 80% (including condensing) | 2134 m (7000 ft) above sea level |
| Wet bulb temperature | 21°C (69.8°F) | 27°C (80.6°F) |
| Front | Back | Side1 |
|---|---|---|
| 915 mm (36 in.) | 915 mm (36 in.) | 610 mm (24 in.) |
| 1 Side service clearance is only required when outriggers are on the rack. Side service clearance is not required during normal operation of the rack when outriggers are not installed. | ||
Rear door heat exchanger
Specifications for Power orderable feature code (FC): EC05 - Rear door heat exchanger indicator (Model 1164-95X).
| Width | Depth | Height | Weight (empty) | Weight (filled) |
|---|---|---|---|---|
| 600 mm (23.6 in.) | 129 mm (5.0 in.) | 1950 mm (76.8 in.) | 39 kg (85 lb) | 48 kg (105 lb) |
|
For more information, see Model 1164-95X rear door heat exchanger. |
||||
Electrical
For electrical requirements, see Power distribution unit and power cord options.
Features
The 7953-94X and 7965-94Y rack has the following features available for use:
- Recirculation prevention plate that is installed at the bottom, front of the rack.
- Stabilizer bracket that is installed at the front of the rack.
Caster locations
The following diagram provides the caster locations for the 7953-94X and 7965-94Y rack.