IBM Elastic Storage Server specifications (5105)

Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.

Use the following specifications to plan for your server.

Table 1. Building blocks
Building block Machine type model (MTM)
IBM® Elastic Storage Server Data Server, Management Server, and Protocol Server 5105-22E
IBM Elastic Storage Server expansion model 92 5147-092
IBM Elastic Storage Server expansion model 106 5147-106
Ethernet switch (32 QSFP ports with 100 Gb support) 8831-00M
Ethernet switch (48 SFP28 ports with 25 Gb support, 8 ports with 100 Gb support) 8831-25M
Ethernet switch (48 RJ45 ports with 1 Gb support, 4 SFP+ ports with 10 Gb support) 8831-S52
InfiniBand switch (100 Gb) 8828-G36
Rack 7965-S42
Table 2. Empty rack dimensions1
Width Depth Height EIA units Weight
600 mm (23.6 in.) 1070 mm (42.1 in.) 2020 mm (79.5 in.) 42 166 kg (365 lb)
  1. The rack is equivalent to a 7965-S42 rack. For more information about the 7965-S42 rack, see Model 7965-S42 rack specifications.
Table 3. IBM Elastic Storage Server building block dimensions

Building Block

Width

Depth

Height

EIA units

Weight (Maximum)

IBM® Elastic Storage Server Data Server, Management Server, and Protocol Server (5105-22E)

482 mm (18.97 in.)

766.5 mm (30.2 in.)

86.7 mm (3.4 in.)

2

30.4 kg (67 lb)

IBM Elastic Storage Server expansion model 92 (5147-092)

483 mm (19.0 in.)

968 mm (38.1 in.)

222.2 mm (8.75 in.)

5

With drives: 135 kg (297 lb)

Without drives: 67 kg (147.7 lb)

IBM Elastic Storage Server expansion model 106 (5147-106)

441 mm (17.36 in.)

1139 mm (44.84 in.)

176.4 mm (6.94 in.)

4

With drives: 145.6 kg (321 lb)

Without drives: 43.1 kg (95 lb)

Ethernet switch (32 QSFP ports with 100 Gb support) (8831-00M)

427.8 mm (16.84 in.)

686.8 mm (27.0 in.)

43.8 mm (1.72 in.)

1

11.1 kg (24.5 lb)

Ethernet switch (48 SFP28 ports with 25 Gb support, 8 ports with 100 Gb support) (8831-25M)

438 mm (17.24 in.)

394 mm (15.5 in.)

43.9 mm (1.72 in.)

1

7.52 kg (16.6 lb)

Ethernet switch (48 RJ45 ports with 1 Gb support, 4 SFP+ ports with 10 Gb support) (8831-S52)

440 mm (17.3 in.)

350 mm (13.78 in.)

44 mm (1.77 in.)

1

5.38 kg (11.86 lb)

InfiniBand switch (100 Gb) (8828-G36)

428 mm (16.85 in.)

685.8 mm (27.0 in.)

43.6 mm (1.7 in.)

1

11.97 kg (26.39 lb)

7063-S42 rack (without side covers)

Side covers are 12 mm (0.25 in.) and 20 kg (44 lb) each.

600 mm (23.6 in.)

1070 mm (42.1 in.)

2020 mm (79.5 in.)

42

166 kg (365 lb)

Table 4. IBM Elastic Storage Server building block electrical specifications1,2,3

Building Block

Power (Watts)

Maximum kVA

Thermal (BTU/hr)

Amperes (A) at 200 Volts (V)

IBM® Elastic Storage Server Data Server, Management Server, and Protocol Server (5105-22E)

800 W

0.816

2730 BTU/hr

4.08

IBM Elastic Storage Server expansion model 92 (5147-092)

1200 W

1.224

4096 BTU/hr

6.12

IBM Elastic Storage Server expansion model 106 (5147-106)

1568 W

1.650

5350 BTU/hr

8.25

Ethernet switch (32 QSFP ports with 100 Gb support) (8831-00M)

395 W

0.416

1348 BTU/hr

2.08

Ethernet switch (48 SFP28 ports with 25 Gb support, 8 ports with 100 Gb support) (8831-25M)

165 W

0.174

563 BTU/hr

0.87

Ethernet switch (48 RJ45 ports with 1 Gb support, 4 SFP+ ports with 10 Gb support) (8831-S52)

92 W

0.097

314 BTU/hr

0.48

InfiniBand switch (100 Gb) (8828-G36)

303 W

0.312

1033 BTU/hr

1.56

  1. The input voltage is based on the power distribution unit (PDU) power cord. For more information, see Power distribution unit and power cord options for 7014, 0551, 0553, and 0555 racks.
  2. All drawers that are mounted in the rack are rated 200 - 240 V ac. The power supplies automatically accept any voltage within the rated voltage range. With dual power supplies installed and operating, the power supplies draw approximately equal current from the utility (mains) and provide approximately equal current to the load.
  3. DC power is not supported.
Table 5. Environment requirements
Environment Recommended operating requirements Allowable operating requirements Nonoperating requirements
ASHRAE class   A2  
Airflow direction1   Front-to-back  
Temperature2 18°C - 27°C (64°F - 80°F) 10°C - 35°C (50°F - 95°F) 5°C - 45°C (41°F - 113°F)
Humidity range 5.5°C (42°F) dew point (DP) to 60% relative humidity (RH) and 15°C (59°F) dew point 20% - 80% RH 8% - 80% RH
Maximum rate of change   5°C per 20 hrs  
Maximum dew point   21°C (70°F) 27°C (80°F) 
Maximum operating altitude   3050 m (10000 ft)  
Shipping temperature     -40°C to 60°C (-40°F to 140°F)
Shipping relative humidity     5% - 100%
  1. Nominal cubic feet per minute (CFM) is approximately 2030. Maximum CFM is approximately 4025.
  2. Derate maximum allowable dry-bulb temperature 1°C per 175 m above 950 m.

Electromagnetic compatibility compliance: CISPR 22; CISPR 24; FCC, CFR 47, Part 15 (US); VCCI (Japan); Directive 2004/108/EC (EEA); ICES-003, Issue 4 (Canada); ACMA radio communications standard (Australia, New Zealand); CNS 13438 (Taiwan); Radio Waves Act, MIC Rule No. 210 (Korea); Commodity Inspection Law (China); TCVN 7189 (Vietnam); MoCI (Saudi Arabia); SI 961 (Israel); GOST R 51318.22, 51318.24 (Russia).

Safety compliance: IEC 60950-1; UL 60950-1; CSA 60950-1.