If you have fixed rails, you might need to install them into the rack. Use this procedure
to perform this task.
About this task
Note: The system requires 2 EIA rack units (2U) of space.
If present, use the rack-mount template to determine and mark the location, and to attach the
mounting hardware to the rack.
Procedure
- Select the appropriate EIA location unit number for the rails. Each EIA location contains three
(3) holes for mounting hardware. For the purpose of these instructions, each EIA set of holes are
identified as a, b, and c, from the top of each EIA unit to the bottom of each
EIA unit.
- Rotate the locking clamps downward at each end of both rails, to the open position.
Figure 1. Opening the rail clamps
Note: The rails are marked with an L, to designate the left rail, and an R, to
designate the right rail.
Note: You might have to move the alignment pins in the fixed rails before installing the rails in
the rack.
- At the rack front, align the bottom of the right rail with the bottom hole (c) of the
EIA unit selected, in both the front of the rack and the rear of the rack. The locator pins
(A) fit into holes (b) and (c) of the EIA location directly above the lowest
EIA unit used, on both the front and the rear of the rack.
Figure 2. Front of rack rail alignment and nut clip locations
- Rotate the hinged rail latch upward to hold the rail in place against the front EIA support
flange.
- Repeat steps 1 through 5 for the left rail.
Secure both rails to the front EIA support flange (B) by using two M5 x 16mm
screws
- At the rear of the rack, rotate the hinged rail latch upward to hold each rail in place against
the rear EIA support flange.
Figure 3. Rear of rack rail alignment and nut clip locations
- Secure both rails to the rear EIA support flanges (B) by using four M5 x
16mm screws.