High Speed Link (HSL) or PCI bridge card slot I/O bridge failure.
Response
LIC data in the I/O bus VPD could not be accessed. The I/O
Bus identified in the SRC may not have become operational.
If there is a B6xx 6906 reference code, close this problem
in the serviceable event view you are working with
and work the 6906 error.
For this reference code the failing item list presented in
the Service Action Log (SAL), or serviceable event
view you are working with, can be different from the failing
item list documented here. That is due to the differences
in system models and features installed.
If the Service Action Log or serviceable event view
on the hardware management console or service processor is available then use the
failing item list presented there for servicing this
reference code.
If a serviceable event view is not available then use the
failing item list documented here. By following the
procedures in the symbolic FRUs listed here you will isolate
to the correct FRU list based on system model and features
installed.
NOTE: A fiber optic cleaning kit may be required for optical
HSL connections.